OJ UDG Series Instructions Manual Download Page 1

1

INSTRUCTIONS

57004E 06/15 (JRK)

English

The thermostat is an electronic on/off ther-

mostat for temperature control of electric 

underfloor heating by means of an NTC sensor 

located either externally or internally within the 

thermostat. The thermostat has a built-in two-

pole ground fault circuit interrupter (GFCI, Class 

A). The thermostat and GFCI are suitable for 

120-240 V (incl. 208 V) 50/60 Hz power sup-

plies.

The thermostat is for flush mounts in a wall 

socket.

Product programme 

Thermostats with built-in GFCI

UCG-4991    Programmable thermostat incl. 

floor sensor

UDG-4999    Programmable thermostat with 2 

sensors: 

 

floor sensor and built-in room 

 sensor
UTN-4991     Non-programmable thermostat 

incl. floor sensor

Power module with built-in GFCI

USG-4000   Power module without sensor

Mounting of floor sensor (fig. 3)

Floor sensor is supplied from SELV (Safety 

Extra low Voltage) Circuit, allowing the sensor 

to be placed as close to the floor surface as 

desired without having to take special account 

to the risk of shock at the damage to the sensor 

cable. It is not intended that the temperature 

sensor wire shall enter through the wall socket 

mounting box. The sensor cable shall be sep-

erated from LINE and LOAD cables.  Can be 

separated in conduite, inside or outside the 

wall. (see fig. 7) 

Recommended placed in an non conductive 

installation pipe, which is embedded in the 

floor. (fig. 3). The pipe must be sealed in the end 

and placed as high as possible in the concrete 

layer. The sensor cable shall be placed in a sep-

arate pipe or be separated from power cables.

The floor sensor must be centered in between 

the heating cable. 

The sensor cable can be extended up to 90 ft 

(30 m) by means of a separate two-core cable. 

Two remaining cores of a multi-core cable 

which, for example, supplies current to the floor 

heating wires, must not be used. The two-core 

cable must be placed in a separate pipe or be 

separated from power cables.

Other approved floor sensors may be used if 

they comply with the technical specifications 

(see fig. 5).

Mounting of thermostat with built-in sensor

(UDG-4999) (fig. 4)

The room sensor is used for comfort tempera-

ture regulation in rooms. The thermostat should 

be mounted on the wall approx. 5.4 ft (1.6 m) 

above the floor in such a way as to allow free air 

circulation around it. Draughts and direct sun-

light or other heat sources must be avoided. 

Mounting of thermostat

Installation

 TO AVOID ELECTRIC SHOCK, DIS-

CONNECT THE HEATING SYSTEM 

POWER SUPPLY AT THE MAIN 

PANEL BEFORE INSTALLING THE 

THERMOSTAT. 

KEEP THERMOSTAT AIR VENTS CLEAN AND 

FREE FROM OBSTRUCTION.

This thermostat is an electrical product and 

must be installed in compliance with the 

National and/or Local Electrical Code. Instal-

lation must be performed by qualified person-

nel where required by law. The thermostat is 

equipped with a ground fault circuit interrupter 

(GFCI, Class A) which requires that the line 

and load cables are isolated from one another 

for correct operation. The thermostat is designed 

for resistive load only. The resistive load must not 

exceed 15 A (1800 W at 120 Vac / 3120 W at 208 

Vac / 3600 W at 240 Vac).

During a ground fault, the two lines will be cut 

off.

Line cable

Delivers power from the service panel (breaker 

panel or fuse box) to the thermostat.

This cable must only be connected to the ther-

mostat’s line terminals, marked L1 and L2.

1.  Connect power cable to terminals 2 and 3 on 

the back of the thermostat (fig. 2).

Load cable

Delivers power from the thermostat to the heat-

ing cable.

This cable must only be connected to the ther-

mostat’s load terminals, marked load 15 A.

1. Connect heating cable to terminals 1 and 4 

on the back of the thermostat (fig. 2).

The detachable cover on the back of the 

thermostat (fig. 1) is designed to prevent unin-

sulated ground wires from dropping onto the 

terminals after installation has been completed.

Warning

Do not loosen the terminal screws 

further than the mechanical stop. Oth-

erwise this will damage the terminal 

(fig. 2).

Temperature sensor

1.  Use a screwdriver to release the catch and 

remove the front cover (fig. 1).

2.  Connect the floor sensor to the terminals 

marked “sensor”, terminals C and D (fig. 6).

3. Mount the thermostat in the wall socket.

4.  Carefully replace the front cover by first posi-

tioning its upper edge and then clicking it into 

place.

Power module, type USG

If loads of more than 15 A are required, expan-

sion is possible using power modules.

Power modules can be connected to the live 

cable and load cable, see relevant sections.

Maximum distance between thermostat and 

power modules is 80 ft (25 m.)

Use field wiring cable, recommended min. 20 

AWG. Connect A to C and B to D (fig. 6).

Operation

Types UCG and UDG (with built-in clock):

The first time the thermostat is connected,

time and day must be set. The thermostat will 

automatically start up in the menu for setting 

time and day.

Type UTN (without built-in clock):

The actual temperature setting is shown and the 

thermostat is ready for use.

Checking the GFCI

It is important that the GFCI is checked for cor-

rect installation and function upon installation 

and monthly thereafter.

To check the GFCI:

Press the “TEST” button.

The test is successful if the red LED on the 

right of the thermostat flashes once every two 

seconds and “GROUND FAULT” appears on 

the display. If this does not occur, check the 

installation.

Press the “Standby/Reset” button to reset the 

GFCI.

The red LED will stop flashing and the display 

returns to its normal appearance.

If the test fails, repeat the test. If it continues to 

fail, ask an electrician to check the installation.

If, during normal operation, the GFCI trips 

without the “TEST” button being pressed, there 

could be a ground fault! To check whether it 

is a ground fault or nuisance tripping, press 

“Standby/Reset”. If this causes the red LED to 

stop flashing and stay off, it was nuisance trip-

ping and the system is operating correctly. If 

this does not occur, there is a ground fault! In 

case of a ground fault, it is important to have 

the installation checked by a qualified electri-

cian according to local and national regulations.

The red LED on the right of the thermostat can 

indicate four different GFCI states:

1. LED off – NORMAL state.

2. LED flashing slowly (once every two seconds) 

– TRIGGERED state. Try pressing the “Stand-

by/Reset” button to reset the GFCI.

3. LED flashing quickly (five flashes per second) 

– ERROR state. Try switching the power off 

and then back on again. If the thermostat 

re-enters the ERROR state, either the wiring 

is wrong (a GN exists) or the unit is defective 

and must be replaced.

4. LED lit constantly – Internal microprocessor 

malfunction or abnormal fault in hardware! 

Try switching the thermostat off and then 

back on again. If the LED is still constantly 

lit, the GFCI is defective and the thermostat 

must be replaced.

Note: The LED lights up briefly without flashing 

during every power-up.

Programming

See user manual.

www.ojelectronics.com/UDG-download

Type UDG, UCG, UTN, USG

© 2015 OJ Electronics A/S

Reviews: