background image

Technical data completed.

INSTRUCTIONS

Type CPST10

67590B 10/16 (JRK)

CPST10-120/240GA (USG-4000)
Power module without sensor (FLS1260)

Power module

English

If loads of more than 15 A are required, 

expansion is possible using power modules.

The power module is intended to be used with 

underfloor heating.

Power modules can be connected to the live 

cable and load cable, see relevant sections.

The power module has a built-in two-pole 

ground fault circuit interrupter (GFCI).

The power module is for flush mounting in a wall 

socket.

Checking the GFCI

It is important that the GFCI is checked for 

correct installation and function upon installation

and monthly thereafter.

To check the GFCI:

Press the “TEST” button.

The test is successful if the red LED on the

right of the power module flashes once every

two seconds. If this does not occur, check the

installation.

Press the “Standby/Reset” button to reset the

GFCI.

The red LED will stop flashing and the display

returns to its normal appearance. If the test

fails, repeat the test. If it continues to fail, ask

an electrician to check the installation.

Classification

The product is a class II device (reinforced 

insulation) and must be connected to the 

following leads:

Max. load 15 A (resistive load).

The power module is intended to be used with

underfloor heating.

The terminals are suitable for field wiring cables

of 12 to 22 AWG.

Phase L1 (L)

Neutral L2 (N)

© 2016 OJ Electronics A/S

1.

120V

0/120 V

If, during normal operation, the GFCI trips

without the “TEST” button being pressed, there

could be a ground fault! To check whether it is a

ground fault or nuisance tripping, press 

“Standby/Reset”. If this causes the red LED to 

stop flashing and stay off, it was nuisance 

tripping and the system is operating correctly. If 

this does not occur, there is a ground fault! In 

case of a ground fault, it is important to have the

installation checked by a qualified electrician

according to local and national regulations.

power module air vents clean and free from

obstruction. This power module is an electrical

device and must be installed in compliance with 

national and/or local electrical codes. Installation 

must be performed by qualified personnel where 

required by law.

The power module is designed for resistive load 

only. The resistive load must not exceed 15 A 

(1800 W at 120 Vac / 3120 W at 208 Vac / 

3600 W at 240 Vac).

Maximum distance between thermostat and

power modules is 80 ft (25 m.)

Use field wiring cable, recommended min. 20

AWG.

To avoid electric shock, disconnect

the heating system power supply at

the main panel before performing

installation and maintenance work

on the power module. Keep the

Use a screwdriver to release the catch and

remove the front cover (fig. 1).

Carefully replace the front cover by first

positioning its upper edge and then clicking

it into place.

Connect A to C and B to D (fig. 3).

Mount the power module in the wall socket.

1.

onto the terminals after installation has been

completed.

Supply 

Load 

Power

GFCI

Type of Action.....................................Type 2.B

Rated Impulse Voltage............................2500V

Control Pollution Degress................................2

USA - Design Patent No......................D768092

Canada No. ..........................................161353

Connect power cable to terminals 2 and 3

on the back of the power module (fig. 2).

1.

4.

2.

Connect heating cable to terminals 1 and 4

on the back of the power module (fig. 2).

The detachable cover on the back of the

power module (fig.1) is designed to prevent

uninsulated ground wires from dropping

1.

2.

3.

The red LED on the right of the power module

can indicate four different GFCI states:

LED off – NORMAL state.

LED flashing slowly (once every two seconds) 

– TRIGGERED state. Try pressing the 

“Standby/Reset” button to reset the GFCI.

1.

2.

LED flashing quickly (five flashes per second)

– ERROR state. Try switching the power

module off and then back on again. If the

power module re-enters the ERROR state,

either the wiring is wrong (a GN exists) or

the unit is defective and must be replaced.

3.

LED lit constantly – Internal microprocessor

malfunction or abnormal fault in hardware!

Try switching the power module off and

then back on again. If the LED is still 

constantly lit, the GFCI is defective and the

power module must be replaced.

Note: The LED lights up briefly without flashing-

during every power-up.

4.

Power module

Warning

Do not loosen the terminal screws

further than the mechanical stop.

Otherwise this will damage the 

terminal (fig. 2).

Warning

Mounting of the power module

La distance maximum entre le thermostat et les

modules de puissance est 25 m.

Utilisez du câble de construction, minimum

recommandé 20 AWG.

Utilisez un tournevis pour relâcher la 

fermeture et retirez le couvercle frontal (fig.1).

Raccorder A à C et B à D (fig. 3).

Montez le module de puissance dans le

boîtier mural.

1.

2.

3.

Montage du module de puissance

Delivers power from the service panel (breaker

panel or fuse box) to the power module.

This cable must only be connected to the power 

module’s line terminals, marked L1 and L2.

Line cable

According to the following standards:

Power module: UL 60730-1

UL 60730-2-9

CSA E60730-1

CSA E60730-2-9

UL file number: E157297 

GFCI:

UL 943 4th ed.

CSA C22.2 No. 144.1-06

UL Listed for the US and Canada

Delivers power from the power module to the

heating cable.

This cable must only be connected to the power

module’s load terminals, marked load 15 A.

Load cable

CPST10-120/240GA (USG-4000)
Module de puissance sans sonde (FLS1260)

Module de puissance

Français

Si des charges de plus de 15 A sont requises,

une extension est possible en utilisant des

modules de puissance.

Le module de puissance est conçu pour être

utilisé avec des planchers chauffants.

Des modules de puissance peuvent être 

raccordés au câble d’alimentation et au câble 

de charge, voir les sections pertinentes.

Le module de puissance possède un disjoncteur

différentiel de fuite à la terre intégré à deux

pôles (DDFT).

Le module de puissance est prévu pour un

montage encastré dans une prise murale.

évents du module de puissance propres et

libres d’obstruction. Ce module de puissance

est un appareil électrique et doit être installé

conformément aux codes électriques nationaux

et/ou locaux. L’installation doit être effectuée

par du personnel qualifié quand la loi l’exige.

Le module de puissance est conçu pour une

charge résistive uniquement. La charge résistive

ne doit pas excéder 15 A (1800 W à 120 VCA /

3120 W à 208 VCA / 3600 W à 240 VCA).

Pour éviter l’électrocution, coupez

l’alimentation du système de 

chauffage au panneau principal avant 

de faire l’installation et l’entretien du

module de puissance. Maintenez les

Gamme de produits

Avertissement

Ne pas desserrer les vis de bornes

au-delà de l’arrêt mécanique. 

Autrement, cela pourrait endomma-

ger la borne (fig. 2).

Avertissement

.......................... 120/240 Vac 50/60 Hz

........................ max.15 A (resistive load)

...............................1.800 W at 120 Vac

.............................. 3.120 W at 208 Vac

.............................. 3.600 W at 240 Vac

......................... Class A (5 mA trip level)

Construction of Control......................................

Method of Mounting Control..............................

Electronic room thermostat for

regulating electrical underfloor heating.

Independently mounted

control for flush mounting

Reviews: