6 Maintenance
6.1 Burner maintenance
Installation, commissioning, or service of the appliance is to be carried
out by authorized and trained personnel only, adhering to all local
regulations and requirements.
Secure all safety covers, enclosures, and guards with all screws before
start-up. Use appropriate tools.
Cut off power supply to the burner and close the manual shut-off valves
always before any maintenance work. Cutting power is adequate when
just inspecting the device.
Before maintenance, make sure that there is no pressure in the piping.
If required, discharge the pressure.
Check the combustion opening regularly for fouling even during periods
when the burner is out of use. A blockage in the combustion head may
cause a hazard.
If you need help with maintenance issues, contact your nearest
representative or visit the Oilon website (
support.
The burner contains electric and electronic components. Adhere to
rules and regulations from local authorities when disposing. See section
Handling and storing.
Before maintenance
● Cut off power supply.
● Close fuel valves.
● Discharge pressure from piping.
● Disconnect ignition cables.
● Remove rods for adjustable combustion head.
90 (111)
M4219 2305EN