Ofs Softening Control Instruction Manual Download Page 12

 
 

 

 

 

 

12 

 

 

9.3

 

Electrical installation 

 

For the connection of the operating voltage and the external signal lines the back panel of the 
device has to be removed and the four M12 screw joints, placed at the sidewall of the device, 
have to be used. The cable ends must be equipped with wire end ferrules with a maximum cross 
section of 0.5 mm

²

 and placed in the device according to the following descriptions.  

 

 

9.3.1

 

Connection of power supply 

 

The supply voltage of 24 Volt DC will is to connect at the terminals 31/32.  An electrical in-
stalled load of 5 Watt is necessary. The terminal 31 has the positive and the terminal 32 the 
negative potential. An operation with 230 Volt AC is allowed only with the power supply unit 
provided by the manufacturer. 
 
Note: 
For  applications  in  industrial  surroundings  with  high  electrical  leakages  current  it  is  recom-
mended to connect the device to an additional protective grounding. 

 
 

9.3.2

 

Output water hardness by active current loop 

 

The signal is a coded residual hardness signal and the current of 4 … 20 mA represents a re-
sidual water hardness in the range of 0 … 2% or 0 … 10%.  The  current loop 4 ... 20 mA is 
connected to the terminals 17/18. The terminal 17 represents the positive and terminal  18 the 
negative potential.  
The following external requirements for electrical connections have to be complied. 
 

External requirements: 

do not connect external voltage  

 

use passive loop resistance of maximum 250 OHMS 

 
 
9.3.3

 

Connection ON / OFF signal 

 

Softening Control is staying in ON-mode as long as there is no short circuit between the ter-
minals 20/21. It will stay on OFF-mode while both terminals are connected. In this state no 
measurement will be done. With termination of the OFF-Line mode and before starting of the 
normal measurement operation, the sensor stays in soft water for 1 minute. 
 
 
 

 
 
 
 
 
 
 

The OFF-Line mode should be used for some minutes or hours only, for avoid-
ing a non-monitoring of the softening plant as well to protect the sensor system 
against germs. 

 
 

 

ON-Line-Mode 

20            21             

OFF-Line-Mode 

20            21             

Summary of Contents for Softening Control

Page 1: ...Softening Control Instruction Manual Version 1 13...

Page 2: ......

Page 3: ...ter 14 9 3 6 1 Connection mechanical water meter 14 9 3 6 2 Connection electronic water meter turbine with Hall contacts 14 9 3 7 Overview electrical connections 15 10 Commissioning 16 10 1 Setting of...

Page 4: ...4...

Page 5: ...ce incorrect or unauthorized intervention of the device or its components incorrect analytical mechanical or electrical effects of any kind damages or subsequent damages due to incorrect operating dam...

Page 6: ...safe and hazard free operation of the device Caution With disregarding of so marked information the device or sensor could be damaged Warning The disregarding of so marked information may cause injur...

Page 7: ...tion must not exceed the specified voltage The raw water and soft water of the monitored or controlled process must cor respond to the relevant drinking water specifications During operation a constan...

Page 8: ...er and will be evaluated after a preset resting time The measurement cycle can be controlled alternatively by impulses of a connected water meter or a potential free closer By automatic opening and cl...

Page 9: ...value given by a DIP switch The difference value shows the actual efficiency of the softening plant The threshold value can be defined individually in steps of 0 25 up to 10 in refer ence to the row...

Page 10: ...an be installed easily 9 2 Hydraulic installation The hydraulic installation of inlets outlet and hardness sensor is only to be carried out after the unit has been fixed at the wall resp frame as foll...

Page 11: ...h would otherwise reach the sampling valves optional connection water meter optional external signal output power supply unit 100 240 V AC 50 60 Hz reserve connection measurement chamber Ventil RW Ven...

Page 12: ...3 2 Output water hardness by active current loop The signal is a coded residual hardness signal and the current of 4 20 mA represents a re sidual water hardness in the range of 0 2 or 0 10 The curren...

Page 13: ...ED status for displaying of functional status and Malfunctions and possible causes The following external electrical requirements must absolutely be fulfilled External requirements maximum connection...

Page 14: ...ng alarm caused of the so called hardness breakthrough it is recommend to monitor the soft water sampling not within fixed time distances Therefore it is possible to connect a mechanical or electrical...

Page 15: ...oop resistor 250 Ohm 18 4 20 mA Loop resistor 250 Ohm 20 Offline contact Potential free contact 21 Offline contact Potential free contact 23 Water meter or potential free closer Potential free contact...

Page 16: ...d Accord ing this decision a connection of contact wa ter meter and setting of DIP switch 4 is to realize The threshold value to be monitored is to set up with the DIP switches 1 3 The following proce...

Page 17: ...1 DIP 2 DIP 3 Threshold value Example With a raw water hardness of 5 0 mmol l alarm will be signalized at ON ON ON 0 25 0 013 mmol l OFF ON ON 0 50 0 025 mmol l OFF ON OFF 1 00 0 05 mmol l OFF OFF ON...

Page 18: ...evaluated accordingly LED Display Evaluation Example green LED lights up water hardness 80 threshold value threshold value 1 water hardness 0 8 green and yellow LED are lighting up water hardness 90 t...

Page 19: ...ves for tightness clean or change valves green and red LED is flashing sensor not recognized Service alarm The measuring system has no elec trical contact to the hardness sen sor check the plug in con...

Page 20: ...e external and manually closed whereby the raw water cannot be flushed out of the measuring chamber by the soft water With repeated recognition of the exceeded threshold value the relevant threshold v...

Page 21: ...sed and with internal humidity a delivery without prejudice is realized A comparison of the number on the sensor with the numbers indicated at packaging and delivery note is rec ommended Further the s...

Page 22: ...sor is mounted and remove the sensor straight from the flow measuring chamber 4 Take the new sensor out of the box and pull it out of the protective cap straightly Do not touch or damage the sensible...

Page 23: ...sensor depending on concentration and duration A strong deep black colouring of the metal electrodes indicates high chlorine influence The sensor may indicate threshold value exceeding while no thresh...

Page 24: ...LED are flashing sensor cable is not properly plugged in or electrical plug in connection defective examine the electrical connection between sensor and device all LED are flashing Sensor performance...

Page 25: ...nsor Protect the sensible sensor part by a protective cap filled with approx 1 ml raw water Store the sensor in a cool 10 15 C and dark place 14 Dismounting 1 Take the device out of operating as descr...

Page 26: ...ter 0 18 mmol l up to 10 8 mmol l natural water Evaluation of water hardness in raw water 100 Evaluation of water hardness in soft water parameterizable threshold value between 0 25 and 10 in referenc...

Page 27: ...rangezogen For verification in accordance with Low Voltage Directive 2014 35 EU the following standards were applied EN 61010 1 2010 Zum Nachweis entsprechend EMV Richtlinie 2014 30 EG wurden folgende...

Page 28: ...OFS Online Fluid Sensoric GmbH Heidelbergweg 9 07580 Ronneburg Germany Manual Softening Control Version 1 13 Issue 12 2018 Subject to technical changes...

Reviews: