9.3.1.
Terminal assignment Softcontrol Data/F
The electrical connection is made according to the following table
(only connected terminals listed):
term. assignment
comment
colour
1
GND
Supply voltage ground
brown
2
U
On
Supply voltage 24V
white
3
GND
GND – sensor
white
4
DS
Sensor
black
5
GND
GND - sensor
black
6
Sens-
Sensor
brown
8
Sens+
Sensor
blue
13
4..20mA
Measured value output 4…20mA (GND)
user
14
4..20mA
Measured value output 4…20mA (+)
user
15
Valve SW GND GND
brown
16
Valve SW 24V
24V
white
17
Valve RW GND GND
brown
18
Valve RW 24V
24V
white
19
Switching output 1
potential-free fault message limit value alarm
user
20
Switching output 1
potential-free fault message limit value alarm
user
21
Switching output 2
potential-free fault message
limit value (sensor) alarm
user
22
Switching output 2
potential-free fault message
limit value (sensor) alarm
user
25
Input 1 – GND
Offline – potential-free contact
user
26
Input 1 – 24V
Offline – potential-free contact
user
27
Input 2 – GND
Water meter – potential-free contact
user
28
Input 2 – 24V
Water meter – potential-free contact
user
29
Input 3 – GND
External alarm or SALIS sensor
– potential-free contact
user
30
Input 3 – 24V
External alarm or SALIS sensor
– potential-free contact
user
31
Input 4 – GND
Enable measurement – potential-free contact
user
32
Input 4 – 24V
Enable measurement – potential-free contact
user