1. DESCRIPTION  OF THE INSTRUMENT 

Series 10 level switches are designed to be mounted in tanks horizontally trough threaded or flanged pipe 
connections. The standard model is fitted with an electrical contact for high or  low-level alarm. Series 10 is 
recommended for use with clean liquids.  

2. DESIGNATION OF THE MODEL 

The designation of the model is explained in the general catalogues. The instruments we supply are always 
identified by a serial number on the data plate of the instrument, which is fastened on the housing of the 
instrument.  

3. OPERATING PRINCIPLE 

When the level of the fluid to be controlled changes, it causes the float (6) to which a permanent magnet (5) is 
fastened to turn. In turning, this magnet rotates a second magnet (8) mounted on the switch group (9) which 
controls the microswitch. A wall of non-magnetic material, capable of withstanding the tank’s pressure, is fitted 
between the two magnets.  

4. INSTALLATION 
CAUTION : Before installing the instrument, make sure that the magnet has not attracted any metal particles.  

MOUNTING ON THE PLANT 

- The place where the instrument is installed on the tank must leave sufficient clearance to disassemble it. The 

float within the tank must be in a position where it is not affected by any turbulence of the liquid. If this is not 
possible, protections must be provided to eliminate the turbulence. 

-Before installing the instrument, make sure that the flanged attachment is large and long enough (the float must 

fit into the tank) and that the attachment is perfectly horizontal (max. 0.5 ° angle) and with a max. 1 ° 
misalignment if flanged. 

- The instrument must be fitted with the electrical connection facing downward.  

ELECTRICAL WIRING 

- The instrument is fitted with a terminal block situated inside the housing which is accessible by removing the 

threaded cover. 

- The terminal block is provided with three terminals ( NC - C - NO ) which are referred to the  absence of liquid. 

Before connecting the power supply, make sure that the housing is closed.                         