INSTALLATION, OPERATION, 

SERVICE, AND REPAIR MANUAL 

 

DAB BLUE DIVER SERIES SUBMERSIBLE 

DEF PUMPS 

 

MODEL NUMBERS: 

BD-750, BD-1000, and BD-1200

 

 
 

 

 

 

 

Summary of Contents for DAB BD-1000

Page 1: ...0 Cedar Springs Road Spartanburg SC 29302 Tel 1 800 500 9311 Tel 864 573 9200 Fax 864 585 3635 www oecfh com INSTALLATION OPERATION SERVICE AND REPAIR MANUAL DAB BLUE DIVER SERIES SUBMERSIBLE DEF PUMP...

Page 2: ...lue Diver Installation Diagram 7 7 3 Before Installation 8 7 4 Pump Discharge Piping for Blue Diver 1200 Only 9 8 0 Cleaning The Blue Diver Filter 9 9 0 Electrical Connection 10 9 1 Electrical Warning...

Page 3: ...installed The entire operation must be carried out in a workmanlike manner Failure to comply with the safety regulations not only cause risk to personal safety and damage to the equipment but invalid...

Page 4: ...ivery 2 25 GPM Liquid Temp Range 33 F to 90 F Max Immersion 33 Ft Storage Temp 33 F to 100 F Relative Humidity of Air MAX 99 Minimum Positive Head 6 Inches Max Starts Per Hour 30 Max Voltage Variation...

Page 5: ...bility The Manufacturer does not vouch for correct operation of the pumps if they are tampered with or modified run outside the recommended work range or in contrast with the other instructions given...

Page 6: ...nk in which the pump is being installed must be vented in accordance with manufacturer s installation instructions Follow the tank manufacturer s tank installation instructions The use of NPT threaded...

Page 7: ...DEF Dispenser 4 Control Panel for Pump Protection 5 Level Control Sensor 6 Tank Fill 7 Pressure Vacuum Vent 8 Man Hole Cover Not Shown 9 Discharge Pipework 10 DEF Storage Tank Courtesy of Containment...

Page 8: ...ctric cable The pump should not touch the tank bottom It should be suspended at least 3 inches from the tank bottom Minimum liquid level should be no less than 6 inches above the bottom of the pump Fa...

Page 9: ...embly and check valve must be installed as shown in Fig 7 4 for the Blue Diver 1200 The bypass assembly ensures that when energized there will always be flow through the pump Blue Diver pumps rely on...

Page 10: ...required for safe installations the above ground metal plumbing should be connected to the power supply as a ground as described in Article 250 80 of the National Electrical Code or Section 26 954 of...

Page 11: ...s of less than 32 F the pump body must be completely emptied to prevent possible cracking of the hydraulic components This operation is advisable even in the event of prolonged inactivity at normal te...

Page 12: ...s characteristics A Remove the obstructions as indicated in the chapter on Warnings Paragraph 6 4 B Change the impellers or remove the obstruction C Check good operation of the valve and replace it if...

Page 13: ...warranted 18 months from date of installation or 24 months from date of manufacture Our Warranty will not apply to any product that in our sole judgment has been subject to negligence misapplication...