Support IAP download, it supports for updating the firmware program in the product
through the network port.
◆
RS485 with surge protection, built-in bias circuit, strong stability. An external
terminal resistor is required.
◆
The data packet sending interval can be adjusted freely, making it more flexible to
use.
◆
The device comes with a powerful diagnostic function to monitor the
communication status in real time.
◆
Support one-key reset function to restore factory settings.
◆
35mm standard rail installation.
◆
EMC complies with EN 55022:2010 & EN55024:2010 international standards.
1.3 Technical parameters
The technical parameters of this product are shown in Table 3.1. Please use this
product within the parameters of this product to obtain better performance.
Table 3.1 Technical parameters
ODOT-S1E1
ODOT-S2E1
Environmental parameters
Working temperature
-40~85℃
Storage temperature
-55~125℃
Operating humidity
5%~95% (No condensation)
The power supply parameters
Number of power
ports
1 road
Input voltage
9-36V
(
DC
)
3KV isolation voltage
Power consumption
Max.100mA@24V
Ethernet parameters
Working mode
Transparent transmission mode, address mapping mode
optional, Modbus TCP protocol
Number of Ethernet
ports
2 RJ45, 2KV surge protection, 10M, 100M adaptive rate 1
Network protocol
ETHERNET
、
ARP
、
IP
、
TCP
、
ICMP
Number of TCP
connections
Max 5
Serial port parameters
Quantity of serial port
Dual RS485