BA_OTE 3+4_Endkunde_EN_V03_20170726.docx
Page 10 of 52
5.4
Temperature image
The temperature image gives an overview of the condition and temperatures of direct
heating circuits and mixing circuits.
5.5
Operational data
Operational data
Description
02-051 Status heating circuit
0 = switched off
(e.g. heating limit exceeded)
1 = normal heating mode
3 = economy heating mode
Heating operation (reduced set value)
4 = frost protection mode
Control to "frost protection temperature" to avoid the heat-
ing circuit freezing up.
6 = hot water priority
(Heating circuit OFF during de-icing)
7 = holiday mode
8 = party mode
9 = normal cooling mode
11 = economy cooling mode
Cooling operation (reduced set value)
13 = manual operation
15 = party mode cooling
16 = drying: heating phase
(floor screed heating programme active)
17 = drying: steady phase
(floor screed heating programme active)
18 = drying: cooling phase
(floor screed heating programme active)
19 = drying: final phase
(floor screed heating programme still active)
22 = cooling mode extern
(cooling to external set value input)
23 = heating mode extern
(heating to external set value input)
00-000 Outdoor temperature
Current outside temperature
02-020 Outdoor temperature av-
erage value
Mean outside temperature (relevant for heat-
ing/cooling limit)
HEATING CIRCUIT 1
ESC
MENU
Outside temperature (
TA
)
Room temperature (
TI
) (only if there is a room unit)
Flow temperature
Depending on the type of system, the measured val-
ue will be taken from one of the following sensors:
- Buffer tank in system
(TPO)
- no buffer (direct heating circuit (
TWV
))
- mixed heating circuit (
TMK
)
Heating circuit pump (
HKP
) ON-OFF