INSTALLATION | Rectifying faults
BIA-EUROPA Mini IWP-EN12 | www.ochsner.com 29
12. Rectifying faults
Fault
Possible cause
Remedy
DHW temperature too low
Water consumption too high
Reduce consumption or switch on auxiliary heater
DHW target temperature set too low
Check DHW target temperature
Measured value F1 not correct
Check sensor F1
Outdoor air too cold (heating output too
low)
Switch on auxiliary heater
DHW circulation in continuous operation
Check time switch, check thermostat and non-return valve
Non-return valve sticks
Release the valve by tapping it slightly
Heating gate valve open
Close gate valve
Defrost active
Wait 20 min
Compressor running and fan not
running
Start capacitor defective
Replace; contact customer service
Winding damage
Replace; contact customer service
Compressor and fan run without
heating the water
No air flow, evaporator dirty
Clean evaporator with water
Evaporator iced-up
Defrost
Air lines clogged
Unclog
Insufficient refrigerant
Contact customer service
Expansion valve does not open
Contact customer service
Compressor not running, fan run-
ning
Starting facility faulty
Replace; contact customer service
Compressor defective
Replace; contact customer service
Continuous water leakage
Safety valve does not close
Vent or replace
Tank defective
Turn off the supply line
Tank drips
Check seals, retighten if necessary
Water discharge, only when heat
pump is running
Condensate
Turn off the supply line
Condensate drain blocked
Clean the drain
Odour
No siphon in the condensate drain
Install
No water in the siphon
Fill
Noise
Gurgling sound
Water level in siphon too low; refill
Rippling noise
Condensate drain blocked; clean
No indication
no voltage 230 V
Check the safety device on the main distributor board for
your house. Switch the safety device back on. If the safety
device triggers again after being switched back on, contact
a qualified contractor or OCHSNER Customer Service.
Electric immersion heater switched
on but not heating
Superheating
Acknowledge safety thermostat
Electrical supply defective
Replace
Er 36
High pressure shutdown
(acknowledge with OK)
Measured value F1 not correct
Check sensor F1
DHW tank not filled with DHW
Filling the system with drinking water
Refrigerant circuit
Contact customer service
Condenser silted up or calcified
Clean, renew
Er 47 defrost fault
(acknowledge with OK)
Intake temperature too low
Heat pump operating program = off and temporarily heat
with electric immersion heater
Er 57 Heat source frost protection
(automatic acknowledgement)
Intake temperature too low
Heat pump operating program = off and temporarily heat
with electric immersion heater.
Install the ventilation flaps!
Flashing HP symbol
Term expiry after 1.5 to 2 years
Renew / check anodes, have time counter reset by heating
contractor