OPERATION | Making settings
22
www.ochsner.com | BIA-EUROPA Mini IWP-EN12
External target value increase (parameter B15=13)
If the electricity tariff is favourable, the target can be in
-
creased. All active heat generators then control to the
target value for anti-legionella mode.
A Target
4.11 Requesting operating data
Symbol
Parameter
Designation
Unit
Pset
Info
H10
Actual value of temperature sensor F1
°C
H15
Actual value of temperature sensor F2
°C
H20
Actual value of temperature sensor F3
°C
H25
Actual value of temperature sensor F4
°C
T14
Compressor operating hours
0…9999 hours
T15
Compressor operating hours
10,000-hour counter (overflow of t14)
T16
Operating hours of the fixed electric immersion heater
0…9999 hours
T17
Operating hours of the fixed electric immersion heater
10,000-hour meter (overflow of t16)
T18
Charging pump operating hours
0…9999 hours
T19
Charging pump operating hours
10,000-hour counter (overflow of t18)
T20
Defrost period
0…9999 hours
T21
Defrost period
10,000-hour counter (overflow of t20)
T24
Operating hours of the variable electric immersion heater
0…9999 hours
T25
Operating hours of the variable electric immersion heater
10,000-hour meter (overflow of t24)
t28
Compressor operating hours since last service
0…9999 hours
t29
Compressor operating hours since last service
10,000-hour counter (overflow of t28)
4.12 Reset to default settings
Symbol
Parameter
Designation
Description
PSet
PA1
J2
Reset controller parameters
2 = Reset controller parameters
0 = default setting
PSEt
PAL
J2
Reset display parameters
(operating programs and time
programs)
Enter password: -19 to access parameters
4 = Reset display parameters
0 = default setting