Buffer sensor (TPO, TPM)
Two buffer sensors are required in the buffer tank.
The heat pump is switched on based on readings
from the TPO and switched off based on those
from the TPM.
-
Install a sensor pocket in the female socket
provided for the upper buffer sensor (TPO)
-
Install a sensor pocket in the female socket
provided for the lower buffer sensor (TPM)
NOTE
In systems with
direct heating circuit,
install the TPO sensor in the heating
flow of the heat pump indoor unit.
-
Install the TPO sensor in the indoor
unit at the marked location on the
heating flow pipe, downstream
from the electric booster heater
(MFA).
-
The required controller parameters
are set by OCHSNER customer
service or specialist personnel
authorised by OCHSNER.
In systems with a buffer tank, a bypass
or a low loss header or a heating
circuit with mixing valve, the TPO
sensor must
not be installed in the
indoor unit
.
Figure 44: Pipe marking in the heat pump indoor unit
Summary of Contents for AIR BASIC 211 T201
Page 50: ...982017 AIR BASIC Multitower T201 EN01 docx Page 50 of 60 11 8 Declaration of conformity...
Page 51: ...982017 AIR BASIC Multitower T201 EN01 docx Page 51 of 60...
Page 52: ...982017 AIR BASIC Multitower T201 EN01 docx Page 52 of 60...
Page 53: ...982017 AIR BASIC Multitower T201 EN01 docx Page 53 of 60...
Page 54: ...982017 AIR BASIC Multitower T201 EN01 docx Page 54 of 60 11 9 ERP Data...
Page 55: ...982017 AIR BASIC Multitower T201 EN01 docx Page 55 of 60...
Page 57: ...982017 AIR BASIC Multitower T201 EN01 docx Page 57 of 60...
Page 58: ...982017 AIR BASIC Multitower T201 EN01 docx Page 58 of 60...
Page 59: ...982017 AIR BASIC Multitower T201 EN01 docx Page 59 of 60...