Oblica FOCUS SERIES Installation And User Manual Download Page 1

GYROFOCUS: 

INSTALLATION AND 

USER MANUAL

1. TECHNICAL DATA 

2

2. PRE-INSTALLATION 

3

3. INSTALLATION 

5

4. OPERATION 

11

5. TESTING 

12

Keep for future use

OBLICA

200 Argyle St 

Fitzroy VIC 3065

03 9416 0400

Summary of Contents for FOCUS SERIES

Page 1: ...GYROFOCUS INSTALLATION AND USER MANUAL 1 TECHNICAL DATA 2 2 PRE INSTALLATION 3 3 INSTALLATION 5 4 OPERATION 11 5 TESTING 12 Keep for future use OBLICA 200 Argyle St Fitzroy VIC 3065 03 9416 0400...

Page 2: ...UNDER TEST CONDITIONS Nominal thermal output 6kW Efficiency 57 8 WEIGHT AND DIMENSIONS Firebox diameter 1250mm Firebox weight 92Kg Flue diameter 219mm Flue weight 16Kg meter Standard bracket weight 20...

Page 3: ...Install the internal flue and engage the firebox Ensure the floor has adequate protection CAUTION Using components or parts other than those provided by the manufacturer or modifying the specification...

Page 4: ...required on all sides when the GyroFocus can rotate 360 100 100 520 Non Combustible Non Combustible 1200 1200 Combustible FULLY ROTATING Combustible Combustible FIXED 500 500 Glass frameless or alumin...

Page 5: ...within the roof as shown in the diagram below The largest cylinder must project down from the ceiling by at least 150mm BCA requirement unless the ceiling is made from a non combustible material such...

Page 6: ...PAGE 6 OBLICA GYROFOCUS INSTALLATION AND USER MANUAL 3 INSTALLATION CONTINUED Custom Length Angle 1 2 25 150 PITCHED ROOF INSTALLATION CUSTOM MADE BRACKET...

Page 7: ...installed as per Australian standards see diagrams below The top of the flue must be 400mm higher than the highest point of the roof Alternatively there must be a minimum distance of 3 meters from an...

Page 8: ...ring holder M12 nuts Safety split pin 3 3 Installing the internal flue 1 Position the single skin flue inside the suspension bracket and tighten the grab screws Ensure that the flue is perfectly verti...

Page 9: ...the combustible floor is installed on concrete you can replace the combustible material with non combustible material laid directly onto the concrete Joist 300mm 300mm Insulative board 20mm non combus...

Page 10: ...loor protector Concrete 300mm FIREBOX Combustible floor eg timber Combustible floor eg timber 20mm e finish 300mm Non combustible finish eg tiles non combustible finish Floor protector Concrete 300mm...

Page 11: ...s to start or rekindle the fire Do not use flammable liquids or aerosols in the vicinity of the fireplace when operating Do not store fuel within prescribed installation clearance distances The use of...

Page 12: ...le fireplace WORK REQUESTED Measure CO2 levels as outlined in AS NZS 4013 1999 to determine if appliance is excluded from full testing to this standard TEST DATES 21 05 2010 RESULTS The maximum carbon...