42
149-157
%
for 2 seconds shuts down
158-176
%
for 1 seconds shuts down
177-187
%
for 0.32 seconds shuts down
>
188
%
for 0.16 seconds shuts down.
Buzzer continuously alarms.
Efficiency
100%
Linear
Load
Line Mode
> 84.5%
> 85%
> 84.5%
Battery
Mode
> 82.5%
> 82.5%
> 82%
ECO Mode
> 90.5%
> 90.5%
> 90.5%
Battery
Battery Number
3
Battery Voltage
36 V
DC
Battery Type
12V
DC
lead-acid battery (Selected and Installed by customer)
Backup
Time
with
Internal
Battery
100%
Load
> 8 min
> 5 min
> 3 min 15sec
50% Load
> 22 min
> 14 min
> 10 min
Charging
Voltage
Floating
Mode
40.95 V
DC
±1%
Bulk Mode
42.3 V
DC
±1%
Charging
Current
Standard
1.8A ± 0.2A
Additional
3.7-4.1 A
Transfer time
Line Mode to Backup
Mode
0 ms
Inverter to Bypass
≦
8ms
Protection Full Protection
Short Circuit / Overload / Over Temperature / ABDM / EPO
DC start
Yes
Self-
diagnostics
Upon Power-on, Front Panel Setting & Software Control, 24
hours routine check
Physical (RT)
Dimensi
ons
(W x H x
D)
inches
17.32 x 3.46 x 27.68
mm
440 x 88 x 703
Weight
lbs
46.3
kg
21
Audible Alarm
Battery Mode
Sounds once every 1.5 seconds (Sounds once every 0.2
seconds for low-voltage battery alarm)
General Alarm
Sounds once every 3 seconds
Overload
Continuously Sounds
Fault
Continuously Sounds
Front Panel
LCD (Standard)
Normal, Battery, Bypass, Self-Test, Battery Weak & Bad,
Site Wiring Fault, Fault, Overload, and Load/Battery Level
LED (Optional)
Button
ON / OFF / Enter / Function / Up / Down
Environmental Operating
Temperature
Operating: 0ºC ~ 40ºC (32ºF to 104ºF) / Storage: -20ºC ~
60ºC (-4ºF to 140ºF)