background image

14U 14-slot ATCA Shelf

Quick Start Guide

Product Number:

11990-190

Doc-No: 63972-373_R1.0

July 2018

Summary of Contents for SCHROFF 11990-190

Page 1: ...14U 14 slot ATCA Shelf Quick Start Guide Product Number 11990 190 Doc No 63972 373_R1 0 July 2018...

Page 2: ...ted by certified Quality Management System to EN ISO 9001 2000 The company cannot accept any liability for errors or misprints The company reserves the right to amendments of technical specifications...

Page 3: ...Environment 4 2 4 Unpacking 5 2 5 Rack Mounting 6 3 Shelf Power Connection 7 3 1 Shelf Ground Connection 8 3 2 Specification for the Shelf Ground connection cable 8 3 3 Power Entry Module 9 3 4 Intro...

Page 4: ...11990 190 II R1 0 July 2018...

Page 5: ...Shelf Manager User s Manual Order no 63972 243 The documentation is available for registered users at www schroff biz Hazardous voltage This is the electrical hazard symbol It indicates that there ar...

Page 6: ...t and Rear View Figure 1 Shelf Front View 1 Front Cable Tray 6 Slot for Shelf Manger 1 2 ATCA 14 Slot Backplane 7 Shelf Manager 2 3 Front Card Cage 8 Serial Interfaces for the Shelf Managers 4 Fan Tra...

Page 7: ...he upper front and lower rear side of the Shelf 10 Fan Tray 2 13 Rear Cable Tray 11 Rear Card Cage 14 Power Entry Module A PEM A 12 Power Entry Module B PEM B 15 PEM Cover Danger of electrostatic disc...

Page 8: ...hat the rack has adequate ventilation Maintain ambient airflow to ensure normal operation If the airflow is blocked or restricted or if the intake air is too warm an over temperature condition can occ...

Page 9: ...elf must be returned If the packaging is damaged and possible Shelf damage is present report to the shipper and analyze the damage Caution When opening the shipping carton use caution to avoid damagin...

Page 10: ...two persons are needed to accomplish this task We recommend to use a mechanical lift or remove all hot swappable equipment for weight reduction Warning Do NOT stack the Shelf on top of any other equip...

Page 11: ...th PE of the building Warning Although there are fuses in the power entry circuit of the Shelf the power lines have to be protected on rack level with breakers Warning Remove jewelry rings watches bef...

Page 12: ...conductor Recommended two hole lugs with 1 spacing for AWG 3 0 Burndy YAZ272TC38 Burndy YAZ272TC3845 45 Burndy YAZ272TC3890 90 Torque for Bolts M6 5 1 Nm 45 in lb Torque for Bolts M8 12 6 Nm 111 in lb...

Page 13: ...tput branches Over current protection is provided by 50 A fuses in each output branch The power filtering consists of filtered power terminals and a discrete line filter for each power branch The inpu...

Page 14: ...11990 190 Shelf Power Connection 10 R1 0 July 2018 3 5 PEM Front View Figure 4 PEM Front View 1 PEM Cover 2 Input Terminal...

Page 15: ...s at the 48 V and two at the RTN feed as shown in figure 4 Required cable size AWG 2 suitable for min 90 C 194 F maximum length 3 m Recommended cable lug Panduit LCDN2 38D Q or Burndy YA2CL2TC516 or e...

Page 16: ...nection 12 R1 0 July 2018 Figure 5 PEM Wiring PEM RTN 48 60 V Feed B Feed A RTN 48 60 V RTN 48 60 V RTN 48 60 V Feed B Feed A RTN 48 60 V Single cable wiring Split cable wiring PEM RTN 48 60 V PEM RTN...

Page 17: ...13 R1 0 July 2018 3 8 PEM Fuses Figure 6 PEM Fuses 12714800 F101 Fuse Branch 1 50 A 80 V F401 Fuse Branch 4 50 A 80 V F201 Fuse Branch 2 50 A 80 V F501 Fuse Branch 5 50 A 80 V F301 Fuse Branch 3 50 A...

Page 18: ...OOS 3 ETH 0 Link Activity LED yellow On Link Off No Link Blinking Activity 8 Shelf Manager Status LED green Solid Green in Service active Shelf Manager Blinking in Service Backup Shelf Manager 4 ETH...

Page 19: ...e rocker switches and the backplane connector going to the hub board base interface Back position of the rocker switches The ATCA specification requires a base channel interface between the shelf mana...

Page 20: ...wing basic commands For a full list of all CLI commands refer to the Pigeon Point Shelf Manager External Interface Reference Manual Change IP address of the primary Shelf Manager clia setlanconfig cha...

Page 21: ...in a board clia fruinfo IPMI address FRU id Change the speed for a Fan Tray clia setfanlevel IPMI address Fru id speed Info The value for the speed is from 0 to 15 Display the contents of the System...

Page 22: ...feed is divided internally at the PEM in 6 out put branches with 35 A each Overcurrent Protection 50 A fuses on PEM Environmental Ambient temperature long term 5 C 40 C 41 F to 104 F Ambient temperat...

Page 23: ...11990 190 Technical Data 19 R1 0 July 2018 5 1 Shelf Mechanical Dimensions Figure 9 Shelf dimensions...

Page 24: ...11990 190 Technical Data 20 R1 0 July 2018...

Reviews: