3
Heating Cable Repair
52
|
nVent.com
You are now ready to braze the end cap body to the
cable sheath.
Using a large
sizzling
flame (see Appendix E), heat out
the moisture from the cable beginning 12 in (30 cm)
back from the end cap body and stopping 1/2 in (13 mm)
from the end cap body (Figure 67). Immediately proceed
to next step.
Note: Details on heating out (drying out) the
cable may be found in Appendix D.
12"
(30
cm)
1/2" (13 mm)
Sizzling flame
Figure 67: Heat out cable
Reduce
sizzling
flame to a
large
flame (see Appendix E).
Apply white flux around end where the end cap body will
be brazed to the cable sheath. Ensure that the flux is
applied around the entire junction.