89116616
- 16 -
DISPLAYING AND CHANGING PROGRAM VARIABLES
Access:
To view and/or change parameters, press and hold the “Prg” and “Sel” buttons for greater than 5 seconds. Press the
“up” or “down” arrow buttons until “22” is displayed, then press “Sel”. When “S-P” is displayed, press “Sel”.
Navigation:
Press “up” or “down” arrow to display sub-menu, then press “Sel” to select the desired sub-menu. In the sub-
menu, use “up” or “down” to display parameters for viewing or changing and press “Sel”. Use “Prg” button to back out or exit
the menu levels as desired.
Adjust:
Use the “up” or “down” arrow to change the parameter value, then press “Sel” button to save the setting. If the“Sel”
button is NOT pressed, the updated setting will not be saved. Navigate to and change other parameters as desired. When
������
ess “Prg” button to back out or exit the sub-menu to the main menu.
NOTE: The display will revert to normal temperature display mode if no buttons are pressed
for 60 seconds.
MODELS WITH °C CONTROLLER
Cooling turns ON at r01 (setpoint) and OFF at r01 (setpoint) – r02 (differential).
For example, using default values from the table below, cooling will turn ON at 35 °C (setpoint) and turn
OFF at 30 °C (setpoint – differential).
OPERATING PARAMETERS
Parameter
Description
Default Value
Range
r01
Cooling set-point
35°C
20°C to 55°C
r02
Cooling differential
5°C
-
P08
Door Open and/or smoke detected
28
4 or 28
ALARM PARAMETERS
Parameter
Description
Default Value
Range
P16
High Temperature Alarm
55°C
-
P19
Low Temperature Alarm
14°C
-
MODELS WITH °F CONTROLLER
Cooling turns ON at r01 (setpoint) + r02 (differential), and OFF at r01 (setpoint)
For example, using default values from the table below, cooling will turn ON at 87 °F (setpoint) +
(differential), and turn OFF at 80 °F (setpoint).
OPERATING PARAMETERS
Parameter
Description
Default Value
Range
r01
Cooling set-point
80°F
72°F to 120°F
r02
Cooling differential
7°F
-
P08
Door Open and/or smoke detected
28
4 or 28
ALARM PARAMETERS
Parameter
Description
Default Value
Range
P16
High Temperature Alarm
125°F
-
P19
Low Temperature Alarm
40°F
-
OPERATING REAL-TIME CLOCK (RTC) PARAMETERS
Parameter
Description
Default Value
Range
t01
Hour
0
0 to 23
t02
Minute
0
0 to 59
t03
Day
0
1 to 31
t04
Month
0
1 to 12
t05
Year
0
6 to 99
C-NET INDUSTRIAL LTD. | +44(0)121 544 8608 | [email protected] | WWW.CNET-IS.CO.UK
Summary of Contents for S060316G031
Page 1: ...SpectraCool Slim Fit Instruction Manual ...
Page 7: ...89116616 6 C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...
Page 8: ...89116616 7 C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...
Page 9: ...89116616 8 C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...
Page 72: ...89116616 71 NOTES C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...