NuAire Terminator TRA Installation And Maintenance Manual Download Page 1

Unit MUST be installed using the appropriate wall 

mounting plate (see Fig. 4b) and with the longer cowl

dimension running horizontally. 

On inclined roofs, the longer dimension of the cowl must be 

running ACROSS roof slope. Unit can be installed at an angle 

of up to 80

O

from the horizontal with the cowl so aligned.

Introduction

The units are manufactured using a range of six basic cowl

sizes A - F. Impellers are available in axial, mixed flow or 

centrifugal versions. 

Coding:

TRA = Axial Flow, TRM =  Mixed Flow, TRC = Centrifugal 

A given cowl size may serve more than one size impeller. 

e.g. TRA500 & TRA560 use a size C cowl. (Table on page 2).

Each unit consists of a base incorporating a spun venturi plate,

a bridge* from which the motor and impeller are suspended and

a GRP cowl (fig. 1).

Motors are manufactured to BS5000, have sealed for life

bearings and have integral thermal protection which must be

incorporated into the control wiring. Failure to use this device

will invalidate the equipment warranty. 

1.0 Handling

Units must at all times be handled carefully to avoid damage or

distortion. The unit is delivered fully assembled and mounted

on a pallet for ease of handling. When lifting or hoisting units,

care must be taken to ensure that no pressure is applied to the

cowl. Lifting eyes, suitable for all units, are available.

Purlin Box / Curb

Purlin box / curbs are manufactured in galvanised mild steel.

The upper face of the purlin box is fitted with a sealing strip.

When installed, the curb must be securely attached to the 

trimmer angles.

Soaker Sheet

Soaker Sheets can be supplied by Nuaire. Manufactured in high

quality GRP, each sheet is 19500 mm long and can be supplied

to match most roof profiles. The soaker sheets are designed to

be used over a prefabricated curb.

2.0 Installation 

The installation must be carried out by competent personnel in

accordance with the appropriate authority and conforming to all

statutory and governing regulations. 

The unit is delivered completely assembled and a protective skin

prevents damage to the unit.  It is strongly recommended that 

this protective skin is allowed to remain in position for as long

as possible. When neccessary, the skin should be removed

using a sharp knife, taking care not to score the unit surface.

The unit can now be inspected for damage. Any accumulation of

dirt should be removed (see cleaning, page 6).

The unit is designed for roof mounting but can be wall mounted

using the optional wallkit available from Nuaire (see page 3).

2.1 Roof installation

Check that the curb mounting surface is flat and that the seal-

ing strip is in position.  (A suitable mastic may be used as an

alternative).

If backdraught shutters or inlet side guards are to be fitted they

should be installed centrally in the curb.

Curbs other than Nuaire purlin box/curbs should be fitted with

timber capping. On timber capped curbs the units may be

attached using coachbolts or similar.  When attaching to Nuaire

purlin box/curbs the use of TEK self drilling screws (type SF

46516) or self tapping screws is recommended. 

Holes are provided in the skirt of the units base/venturi plate.

(See fig. 5).

2.2 Wall installation

If still assembled, separate the unit and wall plate by removing

the screws and washers from around the unit skirt. Retain the

fixings. Depending on the type of wall, prepare a hole to the

dimensions shown on page 3. For a solid wall, fit the hole with

a timber frame as shown. Drill and fit appropriate wall plugs

and secure the timber frame. On completion, the frame must 

be flush with the outside surface of the wall. 

For installation to a profile sheet wall, fit a suitable timber

frame supported by means of angle-iron sections. The timber

frame should, on completion, be flush with the outside sheet

profile (Fig. 4).

Apply a flexible silicone sealer e.g. Flowseal 32 to the timber

frame and secure the wall plate using suitable coach bolts, 

nuts and washers. On a solid wall installation, apply a fillet 

of sealant between the wallplate and wall.

On profile walls it will be neccessary to ‘flash’ the wall plate.

Flashing strips should extend sufficiently to allow fixing to a

high portion of the profile section. Ensure that the flashing

strips over lap at the four corners. Fill between the top and 

bottom flashing strips with Neoprene profile filler and seal all

external joints and seams with a suitable flexible silicone sealer

such as Flowsil 32. (See Wallplate dimensions fig. 4b).

1

12. 05. 17. Leaflet Number 670506

Terminator

TRA/TRM/TRC Roof Extract Fan

Installation and Maintenance

Figure 1. View of unit

The EMC Directive 

2014/30/EU

  

The Low Voltage 
directive 

2014/35/EU

Nuaire: A Trading Division of Polypipe Limited  

Western Industrial Estate

 

Caerphilly  United Kingdom  CF83 1NA  

T: 029 2088 5911  F: 029 2088 7033  E: [email protected]  W: www.nuaire.co.uk

Summary of Contents for Terminator TRA

Page 1: ...ge Any accumulation of dirt should be removed see cleaning page 6 The unit is designed for roof mounting but can be wall mounted using the optional wallkit available from Nuaire see page 3 2 1 Roof in...

Page 2: ...476 600 1452 1400 1410 250 700 1200 88 0 NOTE Dimensions etc refer to Axial Mixed Flow and Centrifugal units See table CODING COWLS below AXIAL code TRA CENTRIFUGAL code TRC MIXED FLOW code TRM Figure...

Page 3: ...Brick or similar wall prepared to Roof profile prepared to accept accept Wall Plate a Purlin Box Curb Dimensions and Fixing Details cont Figure 4 X Y Z E A C A D B Fixing centres Dimensions mm Code A...

Page 4: ...sure that any such items remaining externally accessible once the equipment is installed are adequately guarded This precaution is necessary to avoid the possibility of accidental injury or death Part...

Page 5: ...provided in the fan base plate to bring wiring out from inside the building 4 4 Connection details Check that the electrical supply is compatible with the unit see unit rating plate Connection details...

Page 6: ...the threaded hole opposite the slit A Carefully tighten the grubscrew until the tapers break allowing removal of the impeller Remove the impeller A B 5 2 Replacement of the impeller Place the impelle...

Page 7: ...ropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations 5 3 For EMC all control and sens...

Reviews: