Leaflet 670916

DECEMBER  2001

QTI  QUIETWINS 
Direct Drive Twinfans

single phase

Introduction

The NuAire QUIETWIN Twinfan Direct Drive range consists
of 4 basic  designs with duties up to a maximum of  1.53m

3

/s.

The  4 models are coded as follows:

QTI

(Internal Duct Mounted) in line unit.

QTE     (External Duct Mounted) in line unit
QTR     (Roof Mounted, end inlet) side discharge unit.  
QTRB  (Roof Mounted bottom inlet) side discharge unit. 

QTI Quietwin 

Units are rectangular in section and have circular rigid spigots at
each end (QTIC).  Matching acoustic flexible connectors are
included and four matching mounting feet are alsosupplied.
The casing is manufactured from coated galvanised steel. Full
size access panels are fitted to the top and bottom faces. These
panels are fully detachable for inspection purposes. The internal
surfaces of the case (including the top and bottom panels) are
lined with a fire retardant acoustic lining material. The units
incorporate two independent motors with high efficiency, for-
ward curved centrifugal impellers running in metal scrolls. The
fans discharge into a common outlet  chamber through a shutter
system that prevents ‘blowback through the standby fan.
The motors are manufactured to  BS 5000  and are suitable for
single phase supply. Airflow and failure monitors are standard as
is Class B insulation. Suitable for operation in ambient tempera-
tures up to 40

o

C. 

Controls

The fans are designed to be used with SMART (S) controls . 

Installation 

I

MPORTANT

The installation must be carried out by qualified personnel
in accordance with the appropriate authority and con-
forming to all statutory and governing regulations eg. IEE,
COHSE etc.

QTI units are supplied for installation into In-Line ductwork
(internal) applications. The mounting feet on the QTI unit
can be employed in surface or suspended applications. 

ISOLATION
Before commencing work ensure the electrical supply is
disconnected.

Installation Ancillaries

Anti vibration mountings and  matching  silencers are available

Units should always be positioned with sufficient space to
allow removal of the access covers and subsequent
removal of fan and motor assemblies etc. 

Quietwin QTI units can be mounted in any attitude
except vertical with the outlet facing down, or inverted
i.e. upside down as  these attitudes the shutters will not
operate satisfactorily.

Ductwork connections must be airtight to prevent loss of  per-
formance. The method of mounting used is the total responsi-
bility of the installer. The QTI unit has an external case side
mounted control module / terminal box and is supplied ready
for connection into the electrical supply.

Rigid Mounting 

Note, the QTI unit and silencer cases have captive M8 nuts
which can be used after removing the M8 screws plugging
them. 

On Resilient Mountings

Suspension rods / fixing screws are not supplied. Drill suitable
holes in the support structure to receive the particular sizes.
Note that the large round washers included in the resilient
mounting kits are for fitting above or below the resilient
mounting as required to safeguard the installation against
break-up of, or damage to, a mounting. In the event of a
resilient mounting failure the washer will support the weight
of the unit.

Suspended from ceiling

Large washers should be fitted BELOW the resilient mounts.

Installation   

and Maintenance

Contents

Page

Introduction

1

Installation

1

Dimensions 2
Electrical information                       

2

AV mountings

3

Silencers  

3

Controls wiring  connections

4

Commissioning the fans

5

Maintenance                                                                   8
Certification

9

Warranty

12

1

Fig. 1. General view of a typical QTI unit. 

Unit must NOT be 
installed with the outlet 
facing downward

Unit must NOT be 
installed inverted
(upside down)

TOP

Summary of Contents for QUIETWINS QTI

Page 1: ...nits are supplied for installation into In Line ductwork internal applications The mounting feet on the QTI unit can be employed in surface or suspended applications ISOLATION Before commencing work e...

Page 2: ...amps amps QTI 1 2040 0 086 0 65 1 3 QTI 2 1320 0 104 0 56 1 5 QTI 3 1260 0 230 1 60 4 5 QTI 4 1140 0 370 1 60 4 7 QTI 5 1110 0 660 2 95 10 QTI 6 1272 1 110 4 84 18 QTI 7 960 1 406 6 30 50 QTI 8 960 1...

Page 3: ...V2 QTI 8 NAV2 A V dimensions Code A B NAV1 30 50 NAV2 40 75 Silencer Attenuation Dynamic attenuation of silencer in dB Octave Band Mid frequency Hz Unit code 125 250 500 1k 2k 4k 8k QTI 1 SIL 8 19 14...

Page 4: ...te Feed the mains cable through the rubber grommet and connect your 230v supply to the terminals marked MAINS See fig 6a 6b Timeclock ON OFF Code ST TC Manual User Control ON OFF Code ST MAN MK Adapto...

Page 5: ...cover for more guidance Pressing the step button will sequence through the options and change the modes as follows 1 FAN 1 in manual mode used for commissioning 2 FAN 2 in manual mode used for commis...

Page 6: ...ssure Reading 6 To be used in conjunction with the commissioning procedure as detailed on page 5 The QTI Quietwin is offered in 8 perfor mance curve sizes numbered 1 8 The eight graphs are shown Split...

Page 7: ...Pressure across manometer tappings Pa Volume flow m3 s Speed 100 75 50 0 0 4 0 5 0 6 0 1 0 2 0 3 0 7 Volume Flow Rate Pressure Reading 150 50 100 250 300 200 350 400 Pressure across manometer tappings...

Page 8: ...in adverse environmental conditions or in heavily polluted air NOTE Failure to maintain the unit as recom mended will invalidate the warranty Lubrication Motors are fitted with sealed for life bearin...

Page 9: ...EN292 1 EN292 2 EN294 EN29001 Applied National Standards BS848 Parts One Two and Five Signature of manufacture representatives Name Position Date 1 C Biggs Technical Director 3 8 01 2 W Glover Manufa...

Page 10: ...lation accessories are supplied with the specified equipment eg wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for suppor...

Page 11: ...11...

Page 12: ...co uk www nuaire co uk Leaflet No 670916 Year Warranty Year Warranty 3 Year Warranty UK only The 3 year warranty starts from the date of delivery and includes parts and labour for the first year The...

Reviews: