NuAire Opus 100-B Installation And Maintenance Download Page 1

1

12. 05. 17. Leaflet Number 670967

Opus 100-B & 150-B

Surface Mounted Extract Fans

Installation and Maintenance

2.0 Introduction

A surface mounted unit designed to serve toilets, store rooms,

small offices, restaurants, smoking areas etc. for installation

on the ceiling or wall of the area served. 

For full specification, dimensions and weights etc. refer to 

catalogue.

The range includes single and twin fan models, air inlet is via

front side mounted filters exiting via a 125mm spigot at the

rear. Back-draught shutters are an optional extra LED indicators

on the case cover provide local run/fail status indication.

3.0 Installation

The installation must be completed by competent persons in

accordance with good industry practice and should conform 

to all governing and statutory bodies i.e. IEE, CIBSE, COHSE,

HVCA etc.

The unit comprises a full-length removable access cover to

reveal and remove fan internals and facilitate first fix 

installation. Ensure that all electrical and ducting services are

compatible to the installation and the desired control function

before proceeding.

4.0 Mechanical installation

Remove the unit internals; release the two M4 cover screws

and remove the cover, lift the electronic control module (about

15mm) to disengage from the base socket. Disconnect the PIR

(if fitted) and unscrew the four M5 x 35mm blower assembly

retaining screws and lift out the fan unit internals. 

Select a solid non-reverberant mounting position with a mini-

mum of 50mm from any side-wall and ceiling. Observe the

footprint detail, particularly the mains cable entry point, mark

and drill the chosen structure and fix the case with appropriate

anchor bolts or screws. Connect and fix.

Figure 1. Wall mounting

Opus fan range

Code

Description

Power/FLC
at full speed

OPUS 100-B

A single fan unit

100W/0.39A

OPUS 100-BP

A single fan unit with

100W/0.39A

integral PIR

OPUS 100-2B

A twinfan unit with

100W/0.39A

run and  standby and
auto duty share

OPUS 100-2BP

A twinfan unit with

100W/0.39A

run and  standby and
auto duty share and
integral PIR

OPUS 150-B

A dual fan unit with

200W/0.78A

both motors running

OPUS 150-BP

A dual fan unit with

200W/0.78A

both motors running
and integral PIR

1.0 Typical arrangements

Figure 2. Ceiling mounting

The EMC Directive 

2014/30/EU 

 

The Low Voltage 

Directive 

2014/35/EU

Note: For EMC the ambient temperature limit for the 

Opus plus range is 24 deg C (or 25 deg if the speed pot 

is restricted to ¼ turn above minimum).

WARNING - 

REMOVE TRANSIT PACKING PIECES BEFORE

APPLYING POWER TO UNIT

Electrical

terminal block

Cable grommet

Motor plate

fixing screws (2)

Motor assembly

Earth post

1

2

Figure 3. Removing the impeller transit-packing pieces (1 and 2).

Nuaire: A Trading Division of Polypipe Limited  

Western Industrial Estate

 

Caerphilly  United Kingdom  CF83 1NA

Ca

T: 029 2088 5911  F: 029 2088 7033  E: [email protected]  W: www.nuaire.co.uk