NuAire Opus 100-2M Installation And Maintenance Download Page 1

1

12. 05. 17. Leaflet Number 671218

Opus 100-M & 150-M

Duct Mounted Extract Fans

Installation and Maintenance

1.0 Introduction

Manufactured in galvanised steel, the unit is designed to

serve toilets, store rooms, small offices, restaurants, 

smoking areas etc. and for duct mounting applications 

usually in the ceiling or service voids above the areas

served. For full specification, dimensions and weights etc.

refer to catalogue.

2.0 Installation

The installation must be completed by competent persons 

in accordance with good industry practice and should 

conform to all governing and statutory bodies i.e. IEE,

CIBSE, COHSE, HVCA etc.

The unit comprises a full length access cover, to reveal 

filter and fans and is supplied with outlet spigot fitted and

‘knockouts’ to be removed at the chosen inlet positions.

Prepare the unit for installation by removing the access

cover, all internal packaging and the fan assembly (which 

is supplied loose in the box). Replace the unit cover and

knock out the chosen inlet spigot points and fit the 

matching spigots.

Ensure that all electrical and ducting services are compatible

to the installation and the desired control function. 

3.0 Mechanical installation

Select a solid non-reverberant mounting position, remove

the unit support bracket and fix the bracket to the chosen

structure with appropriate anchor bolts or screws.

The fan can be installed using the integral mounting bracket 

supplied (Figure 3). Offer the unit to the bracket as shown

and secure into position with the one point-fixing bolt.

Connect inlet and outlet ducting.

Figure 1. General view of unit showing airflow.

Mounting bracket to

structure fixings.

Bracket tongues engage with

case slots, then case rotated

up to align with fixing screw

hole.

Figure 3. 

Bracket tongues

must engage

with case slots.

Opus fan range

Code

Description

Power/

FLC at full speed

OPUS 100-M

A single fan unit

100W/0.39A

OPUS 100-2M

A twinfan unit with

100W/0.39A

run and  standby and

auto duty share

OPUS 150-M

A dual fan unit with both

200W/0.78A

motors running

The EMC Directive 

2014/30/EU

  

The Low Voltage 

Directive 

2014/35/EU

Note: For EMC the ambient temperature limit for the 

Opus plus range is 24 deg C (or 25 deg if the speed pot 

is restricted to ¼ turn above minimum).

WARNING - 

REMOVE TRANSIT PACKING PIECES BEFORE

APPLYING POWER TO UNIT

Electrical

terminal block

Cable grommet

Motor plate

fixing screws (2)

Motor assembly

Earth post

1

2

Figure 2. Removing the impeller transit-packing pieces (1 and 2).

Nuaire: A Trading Division of Polypipe Limited  

Western Industrial Estate

 

Caerphilly  United Kingdom  CF83 1NA

Ca

T: 029 2088 5911  F: 029 2088 7033  E: [email protected]  W: www.nuaire.co.uk