The EMC Directive 
2014/30/EU
The Low Voltage 
Directive
2014/35/EU

NALTM 50 & 60HZ

Metal Cased Centrifugal Fans
Installation and Maintenance

1.0 INTRODUCTION

The NALTM unit is supplied with a pre-wired terminal box and an IP44 rated, 
class B (unit sizes 100-160) or class F (unit sizes 200-315) insulated motor. The 
fans are designed to convey clean air with a maximum temperature of up to 
60°C (NALTM-315H up to 55°C only).
Do not operate the fan in the presence of inflammable vapours (alcohol etc). An 
adequate supply of fresh air must be provided if the fan is to be fitted in a room 
with a gas burning appliance which is not of the balance flue type.

4.0 DIMENSIONS (mm) & Weights (kg)

Figure 1. Unit Drawing

Code Description:
  NALTM-100H
 
 

 

      1          2    3

1.  NALTM - Centrifugal Metal Tube Fan Range
2.  100 - Case Size
3.  No Suffix - 50Hz 230V 
  H - 60Hz 220V

2.0 HANDLING

Always handle the fans carefully to avoid damage and distortion. Care should 
be taken to ensure that any slings used for lifting purposes do not damage the 
casing, connection box, impeller or inlet cone.

3.0 INSTALLATION

Installation must be carried out by a competent person in accordance with the 
appropriate authority and conforming to all statutory and governing regulations 
(e.g. IEE, CIBSE etc.).
From the fan Rating Plate, observe the weight of the unit and select the 
mounting position and structure that can support the unit.
These fans are not for stand-alone use. They are designed to be incorporated  
into ducted systems, machines or where safe (i.e. operation  has been ensured by 
providing applicable protection to moving parts).
This unit is not designed for external use. Before installing ensure the impeller is 
running freely and there are no obstructions to the airflow
A robust mounting foot is available as an accessory, to ease installation.

Figure 2. Unit Dimensions

50 Hz Code

60 Hz Code

A

B

C

D

E

Weight

NALTM-100

NALTM-100H

241

98

196 150

23

3

NALTM-125

NALTM-125H

241

123

198 144

27

3

NALTM-150

NALTM-150H

332 147

212 166

23

5

NALTM-160

NALTM-160H

332

157

221 175

23

5

NALTM-200

NALTM-200H 333 198 223 173

25

5

NALTM-250

NALTM-250H 333 248 206 152

27

6

NALTM-315

NALTM-315H

401

312 230 180

25

8

For good EMC engineering practice, any sensor cables or 

switched live cables should not be placed within 50mm of other 

cables or on the same metal cable tray as other cables.

Isolation - Before commencing work, make sure that the unit, 

switched live and any controls are electrically isolated from the mains 

supply.

Please note that this product must be earthed.

IMPORTANT

5.0 ELECTRICAL WIRING

Electrically isolate unit before commencing any work. Ensure that the voltage 
and frequency of the electrical supply match the information stated on the 
Rating Plate on the unit. Wire the unit as shown in the wiring diagram. On 
connecting the electrical supply, ensure that the airflow direction corresponds 
with the direction of the airflow arrow sited on the unit.

MOTOR

YELLOW-GREEN

BLACK

L N

BLUE

BROWN

Figure 3. Wiring diagram

Electrical Note:

 Because the run and start currents depend upon the duty and 

associated duct work of an individual unit, the values quoted in the table are 
nominal.
Run currents will be exceeded if the unit is operated beyond the operating curve 
shown in the performance catalogue.