NuAire MVHR-LP-AC Installation And Maintenance Download Page 1

1

Leaflet Number 671350 July 2007

Figure 1.

MVHR-LP-AC

Mechanical Ventilation with Heat Recovery

Installation and Maintenance

Figure 3.

Cut through the

acoustic foam round

the circumference of

the damper.

Damper can be

swivelled on the

2 body casing

hinges.

Fixing screw hole.

Bracket tongues

engage with casing

slots, then unit

rotated up to align

with fixing

screw hole.

Slots in casing

either side of

unit to allow

alternative

mounting option.

Figure 4.

When spigot is in

position, damper can

be adjusted using a

screwdriver.

Figure 2.

Discharge

Supply

Supply

Extract

Extract

Intake

Access covers on underside.

1.0 Introduction

The Nuaire MVHR-LP-AC unit is designed to provide

mechanical supply and extract ventilation with heat

recovery.

The unit is fitted with two fans with independant adjustable

speed control. A plate heat-exchange constructed from

aluminium is used to provide up to 70% heat recovery.

2.0 Installation

I

nstallation must be carried out by competent personnel

conforming to all statutory and governing regulations

including the current wiring and CDM regulations.

Special attention must be paid to the size and weight of the

unit and the handling method to locate the unit in situ.

The unit is designed to be ceiling mounted in the horizontal

plane with access panels and condensate drain on the

underside.

The fan must be fitted indoors, away from any direct

sources of heat, water spray or moisture generation.

Temperature range -5

O

C to 40

O

C.

Please note a clear working space is required around

the installed unit to allow the cover to be removed and

provide sufficient access for maintenance such as filter

change.

The fan is designed to be wired direct to the mains supply

through a fused spur isolator (by others).

With the unit fixed in position and working from underneath

the installation bring the mains wiring through the chosen

rubber cable entry grommet at the new connection box.

Additional grommeted holes are provided to allow additional

wiring to each blower.

The integral mounting bracket supplied can be offered up to

position, the fixing points marked through and the bracket

installed with 4 screws (by others).

Offer the unit into position and locate the bracket into the

slots in the case before fixing with the single bracket fixing

screw.

Various damper/inlet spigot positions can be utilised as

required to suit the system ductwork and extract grilles.

To reduce air leakage, spigots should be sealed to the unit

by silicone sealant or similar (by others).

All inlet dampers are ’closed’ as knockouts when delivered

but can be opened using a sharp knife. (See figure 3).

After the spigot has been fixed adjust the damper with a

screwdriver. (See figure 4).

See figure 5 for spigot location and sizes.

The condensate drain must be connected via a trap into

either a suitable waste water system or to the outside of

the building. This connection must be detachable to allow

access into the unit. Ensure the pipe from the condensate

drain falls away from the unit.

Nuaire Limited

Western Industrial Estate Caerphilly United Kingdom CF83 1NA

T: 029 2088 5911 F: 029 2088 7033 E: [email protected] W: www.nuaire.co.uk

Summary of Contents for MVHR-LP-AC

Page 1: ...e note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter change The fan is designed to be wired direct to the mains supply through a fused spur isolator by others With the unit fixed in position and working from underneath the installation bring the mains wiring through the chosen rubber cable e...

Page 2: ... extract 100 dia extract 100 dia supply 100 dia supply 125 dia 100 dia supply supply 125 dia Intake 125 dia discharge Condensate drain 022 OD Weight 25kg N L SL TRICKLE BOOST A B C D E F G N L SL TRICKLE BOOST A B C D E F G 2 0 Dimensions Figure 5 Dimensions in mm N L SL TRICKLE BOOST A B C D E F G 3 0 Electrical Wiring 3 1 Additional Control Wiring Option The two fans are pre wired into an extern...

Page 3: ...damage and security of components Refit covers To remove the drip tray and the heat exchanger remove the screws securing the retainer clips Take care not to let the drip tray and the heat exchanger drop down Clean by washing the parts in tepid water with suitable disinfectant Allow to dry naturally before refitting back into the unit 6 0 Replacement of Parts Should any component need replacing Nua...

Page 4: ...n within the unit is considered Lifting gear such as slings or ropes must be arranged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperatu...

Reviews: