NuAire MRXBOXAB-ECO4 Installation And Maintenance Manual Download Page 1

1

nuaire.co.uk 

029 2085 8400

19. 08. 19. Leaflet Number  671797

MRXBOXAB-ECO4 (Standard Unit)

MRXBOXAB-ECO4-OH (Opposite hand Unit) 

Mechanical Ventilation Units with Heat Recovery and  
Heat Exchanger Bypass for Wall Mounting

 

Installation and Maintenance 

The EMC Directive

 

2014/30/EU

The Low Voltage 
Directive

2014/35/EU

1.0 Introduction

The ECO4 wall mounted units are designed to provide mechanical 

supply and extract ventilation with heat recovery and an integral 

automatic HX bypass.
The units also incorporate an integral humidistat and frost protection 

(see page 7 for details).
To recover heat from the extract air the heat exchanger block is utilised. 

The heat exchanger can recover up to 95% of the normally wasted 

heat.

2.0 Installation

Installation must be carried out by competent personnel in accordance 

with the appropriate authority and conforming to all statutory 

governing regulations. All mains wiring must be in accordance with the 

current I.E.E. Regulations, or the appropriate standards. Ensure that the 

mains supply (Voltage, Frequency and Phase) complies with the rating 

label. 
Please note a clear working space is required around the installed unit 

to allow the cover to be removed and provide sufficient access for 

maintenance such as filter change.
Please allow a minimum of 480mm in front of the unit.
The fan must be installed indoors, on a suitable wall away from direct 

sources of frost, heat and water spray or moisture generation. For a 

vibration-free result the unit must be mounted to a solid wall.

The unit is designed for wall mounting only on a solid wall, a 

gypsum block or a stud wall will not suffice. Additional measures 

such as extra studs or double panelling using 20mm MDF is 

required.

1. One part of the mounting bracket (supplied) should be offered up 

to the wall, ensuring it’s located horizontally. Mark the fixing points 

through the pre drilled holes in the bracket and install with screws (by 

others), whilst ensuring the interlock side is at the top (fig. 3). 
2. Install the unit on the wall by ensuring the bracket on the unit 

interlocks over the wall mounted bracket (fig. 4). Ensure the mains 

power cable does not become trapped between the brackets during this 

process as this will prevent engagement and potentially damage the 

electrical insulation. The cable gland can be rotated through 90 degrees 

to assist this operation and subsequent cable routing.

IMPORTANT

The unit must remain switched on at all times to maintain 

ventilation within the dwelling. Turning the unit off will cause long 

term damage to the unit and building fabric.

This appliance is not intended for use by persons (including children) 

with reduced physical, sensory or mental capabilities, or lack of 

experience and knowledge, unless they have been given supervision 

or instruction concerning the use of the appliance by a person for their 

safety. Children should be supervised so that they do not play with 

the appliance.

Note: Care must be taken to ensure the unit is installed true in 

all 3 dimensions. Failure to do so may result in overflow from the 

internal condensation drip tray.
 If fitting the MVHR in conjuntion with a MRXBOX-SIL4 the unit 

should be mounted using alternative brackets supplied under part 

code MRXBOX-AV4, the standard wall brackets supplied with the 

MVHR are not rated for the additional load.

Extract air 
from house

Intake air 
from outside

Exhaust air 

to outside

from house

Supply air 
to house

Exhaust air 

to outside

from house 

Supply air 
to house

Extract air 
from house

Intake air 
from outside

Figure 1. Airflow through unit (Standard unit).

Figure 2. Airflow through OH unit (Opposite hand unit).

Figure 3. Fixing the mounting bracket to the wall. 

Summary of Contents for MRXBOXAB-ECO4

Page 1: ...mounting bracket supplied should be offered up to the wall ensuring it s located horizontally Mark the fixing points through the pre drilled holes in the bracket and install with screws by others whilst ensuring the interlock side is at the top fig 3 2 Install the unit on the wall by ensuring the bracket on the unit interlocks over the wall mounted bracket fig 4 Ensure the mains power cable does n...

Page 2: ... 5 Typical example of a cupboard mounted unit Standard unit fixed to a stud partition with the MDF panel fixed behind the plaster board 2 3 Condensate Drain 1 The condensate must be discharged under a water level in a U trap drainpipe or an alternative drain method which acts as an airlock 2 The condensate discharge drain is a 32mm male threaded connection 3 If using a U trap please ensure the U t...

Page 3: ...iably fixed to the appliance 2 6 Ventilation Flow Rates 2 7 ADF 2010 Ventilation Calculations Design of MVHR Systems The MVHR system has been sized for the winter period Additional ventilation may be required during the warmer months and it has been assumed that the provisions for purge ventilation e g openable windows could be used Step 1 For any design air permeability determine the whole dwelli...

Page 4: ...m top Side view Front view 18 Mounting Bracket AB AB 200 176 534 67 492 CRS 67 40 0 CRS 5 Fixing Points be fitted to Bracket to Volt Free Cable Exit Point Main Cable Exit Point the wall 40 0 CRS 86 0 Front view Side view 86 0 15 0 23 0 Flush mounting face to wall or back box 25 25 Figure 9 Unit dimensions 3 0 Dimensions mm Figure 10 Dimensions MRXBOX95 3SWITCH Figure 11 Dimensions Unit wall mounti...

Page 5: ...ated supply duct Top of ceiling void Air supply to bedrooms in ceilings via Air Valve mounted unit Nuaire wall MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running to SVP Insulated extract duct New ALSO FROM NUAIRE range of thermal ducting an all in one insulated ducting system see installation document 671780 Exhaust air from kitchen bathroom to outside via air brick Minimu...

Page 6: ...1 2 Fuse 5A 2 Pole Isolator light Room Light switch Double Pole MAINS 230V 50Hz N L 3 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 Fuse 5A Room lights Light switches Double Pole MRXBOXAB ECO4 Figure 15 Unit only Disconnection from the supply mains must be incorporated within the fixed wiring in accordance with the wi...

Page 7: ...nd mould growth The clear panel covering the control has an adhesive panel which should be exposed and sealed post commissioning to prevent tampering 6 0 Switch To fix the switch to a wall or back box remove the front fascia by inserting a terminal screwdriver into the two openings along the bottom edge and prize open gently The fixing points on the back plate can then be accessed once the switch ...

Page 8: ...ive and Nuaire control are electrically isolated from the mains supply and switched live supply Filter covers Filter being removed Filter cover Figure 20 Removing the two filter covers on the front panel of the unit Figure 21 The filters can be removed by pulling on the black tab on the visible end of the filters 12 0 After Sales For technical assistance or further product information including sp...