NuAire MRXBOX-FF4 Installation And Maintenance Download Page 1

1

22. 07. 20. Document Number  671812

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

MRXBOX-FF4

First Fix Plenum Chamber For Wall / Cupboard  
Mounted MRXBOXAB-ECO4 Units 

Installation and Maintenance

1.0 SAFETY INFORMATION

• 

Ducting must be securely fixed with screws to the spigot to prevent access to live parts. Duct 
runs terminating close to the fan must be adequately protected by suitable guards.

• 

This appliance should not be used by children or persons with reduced physical, sensory or 
mental capabilities or lack of experience and knowledge, unless they have been given supervision 
or instruction concerning the safe use of the appliance by a person responsible for their safety. 
Children shall not play with the appliance. Cleaning and user maintenance shall not be carried 
out by children.

1.1 Symbols

 

REFER TO INSTRUCTION MANUAL

 

 

 

Read and understand the installation and maintenance manual before installing,    

 

 

operating or maintaining this product.

1.2 Important Information

This manual contains important information on the safe and 
appropriate assembly, transport, commissioning, operation, 
maintenance, disassembly and simple troubleshooting of the product.

While the product has been manufactured according to the accepted 
rules of current technology, there is still a danger of personal injury or 
damage to equipment if the following general safety instructions and 
the warnings contained in these instructions are not complied with.

Read these instructions completely and thoroughly before 
working with the product.

Keep these instructions in a location where they are accessible 
to all users at all times.

Always include the operating instructions when you pass the 
product on to third parties.

1.3 Personal Protective Equipment

The following minimum Personal Protective Equipment (PPE) is 
recommended when interacting with Nuaire product:

Protective Steel Toed Shoes - 

when handling heavy objects.

 

Full Finger Gloves (Marigold PU800 or equivalent) - 

when 

handling sheet metal components. 

Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent) 

- when conducting light work on the unit requiring tactile 
dexterity. 

Safety Glasses

 - when conducting any cleaning/cutting operation 

or exchanging filters. 

Reusable Half Mask Respirators 

- when replacing filters which 

have been in contact with normal room or environmental air.

Nuaire would always recommend a site specific risk assessment by a 
competent person to determine if any additional PPE is required. 

2.0 INTRODUCTION

Nuaire’s MRXBOX-FF4 is designed for use with MRXBOXAB-ECO4 
MVHR units.  The product offers a first fix installation solution; in 
addition the multiple spigot positions simplify ducting layouts. Each 
chamber is fully lined with acoustic foam offering excellent noise 
reduction. 

3.0  MECHANICAL INSTALLATION

Installation must be carried out by competent personnel in 
accordance with the appropriate authority and conforming to all 
statutory governing regulations.

Please note a clear working space is required around the  
MRXBOXAB-ECO4 installed unit to allow the cover to be removed and 
provide sufficient access for maintenance such as filter change.  Please 
allow a minimum of 480mm in front of the unit.

The fan must be installed indoors, on a suitable wall away from direct 
sources of frost, heat, water spray or moisture generation. 

For a vibration-free result the unit must be mounted to a solid wall.

For more detailed information on structural and installation 
requirements of the MRXBOXAB-ECO4 unit please refer to the 
installation documents supplied with the MVHR unit and also 
MRXBOX-AV4 for wall mounting details.

3.1 Ducting

The metal knock outs and foam lining should be removed from any 
positions that are to be ducted (Figure 1), the 220mm x 90mm spigots 
supplied can then be fitted to these locations using the self-tapping 
fixings supplied.  If no spigot is to be fitted the knock out and foam 
should be left in place and the area blanked off using the hanging 
brackets and self-tapping screws supplied. 

The remaining 200mm diameter spigots should be fitted to the 
underside of the unit using self-tapping screws supplied.  

A bead of silicone must be applied to the perimeter of all spigots 
and hanging brackets fitted to prevent leakage.

Reviews: