MRXBOX-ECO2 (Standard Unit)

MRXBOX-ECO2-OH (Opposite hand Unit) 

MRXBOXAB-ECO2 (Standard Unit) 

MRXBOXAB-ECO2-OH (Opposite hand Unit) 

Mechanical Ventilation Units with Heat Recovery for Wall Mounting

 

Installation and Maintenance 

The EMC Directive

 

2014/30/EU

The Low Voltage 
Directive

2014/35/EU

1.0 Introduction

The ECO2 wall mounted range of units is designed to provide 

mechanical supply and extract ventilation with heat recovery. 
The unit is fitted with two independent fans. Each fan has full speed 

control for background and boost ventilation rates. To recover heat 

from the extract air the heat exchanger block is utilised. The heat 

exchanger can recover up to 95% of the normally wasted heat.

2.0 Installation

Installation must be carried out by competent personnel in accordance 

with the appropriate authority and conforming to all statutory 

governing regulations. All mains wiring must be in accordance with the 

current I.E.E. Regulations, or the appropriate standards. Ensure that the 

mains supply (Voltage, Frequency and Phase) complies with the rating 

label. 
Please note a clear working space is required around the installed unit 

to allow the cover to be removed and provide sufficient access for 

maintenance such as filter change.
Please allow a minimum of 350mm in front of the unit.
The fan must be installed indoors, on a suitable wall away from direct 

sources of frost, heat and water spray or moisture generation. For a 

vibration-free result the unit must be mounted to a solid wall.

IMPORTANT

The unit must remain switched on at all times to maintain 

ventilation within the dwelling. Turning the unit off will cause long 

term damage to the unit and building fabric.

This appliance is not intended for use by persons (including children) 

with reduced physical, sensory or mental capabilities, or lack of 

experience and knowledge, unless they have been given supervision 

or instruction concerning the use of the appliance by a person for their 

safety. Children should be supervised so that they do not play with 

the appliance.

2.1 Wall Mounting the MVHR Unit

The unit is designed for wall mounting, only on a solid wall. A 

gypsum block or stud/plasterboard wall will not suffice.

1. One part of the mounting bracket (supplied) should be offered up 

to the wall, ensuring it’s located horizontally. Mark the fixing points 

through the pre drilled holes in the bracket and install with screws (by 

others), whilst ensuring the interlock side is at the top (fig. 3).

2. Install the unit on the wall by ensuring the bracket fixed to the rear of 

the unit interlocks over the wall mounted bracket (fig. 4).

Note: Care must be taken to ensure the unit is installed true in 

all 3 dimensions. Failure to do so may result in overflow from the 

internal condensation drip tray.

(See overleaf for mounting option details, on walls or 

in the loft space).

Extract air 
from house

Intake air 

Exhaust air 

from outside

to outside

from house

to house

Supply air 

Intake air 
from outside

Extract air 
from house

Supply air 
to house

Exhaust air 
from house
to outside

Figure 1. Airflow through unit (Standard unit).

Figure 2. Airflow through OH unit (Opposite hand unit).

Figure 3. Fixing the mounting bracket to the wall. 

Figure 4. Mounting the unit on the wall mounted bracket.

Summary of Contents for MRXBOX-ECO2

Page 1: ...id wall IMPORTANT The unit must remain switched on at all times to maintain ventilation within the dwelling Turning the unit off will cause long term damage to the unit and building fabric This applia...

Page 2: ...tray assembly is to be purchased separately Part No MRXBOX AV2 2 5 Option 2 Loft Space Mounting The MVHR unit should be positioned on a 25mm minimum thickness MDF panel that is vertically fixed acros...

Page 3: ...F 2010 Extract ventilation rates Table 2 Whole dwelling ventilation rates Notes 1 In addition the minimum ventilation rate should be no less than 0 3 l s per m2 of internal floor area This includes al...

Page 4: ...e as follows The maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least tho...

Page 5: ...ted supply duct Top of ceiling void Air supply to bedrooms in ceilings via Air Valve mounted unit Nuaire wall MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running to SVP Insulat...

Page 6: ...ons in fig 15 are factory fitted The unit is pre wired with a 2 metre fly lead Figure 16 View of the base on the unit showing the position of the connector for Ecosmart devices located next to cable e...

Page 7: ...on to solely boost the unit Additional switch should be used local to the wet rooms see wiring diagrams 7 0 Status Indication The status of the unit is indicated by a series of LED s on the front cov...

Page 8: ...number of the unit and the ARC number of the purchase if possible This information will be available on the fan label 11 0 Warranty The 5 year warranty starts from the day of delivery and includes pa...

Reviews: