![NuAire MRXBOX-AV4 Installation And Maintenance Download Page 1](http://html1.mh-extra.com/html/nuaire/mrxbox-av4/mrxbox-av4_installation-and-maintenance_1715881001.webp)
1
28. 07. 20. Document Number 671814
Nuaire |
Western Industrial Estate
|
Caerphilly
|
CF83 1NA
|
nuaire.co.uk
MRXBOX-AV4
Anti-Vibration Mounting Assembly For
MRXBOXAB-ECO4 Units
Installation and Maintenance
1.0 SAFETY INFORMATION
•
This appliance should not be used by children or persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge, unless they have been given supervision
or instruction concerning the safe use of the appliance by a person responsible for their safety.
Children shall not play with the appliance. Cleaning and user maintenance shall not be carried
out by children.
1.1 Symbols
REFER TO INSTRUCTION MANUAL
Read and understand the installation and maintenance manual before installing,
operating or maintaining this product.
1.2 Important Information
This manual contains important information on the safe and
appropriate assembly, transport, commissioning, operation,
maintenance, disassembly and simple troubleshooting of the product.
While the product has been manufactured according to the accepted
rules of current technology, there is still a danger of personal injury or
damage to equipment if the following general safety instructions and
the warnings contained in these instructions are not complied with.
•
Read these instructions completely and thoroughly before
working with the product.
•
Keep these instructions in a location where they are accessible
to all users at all times.
•
Always include the operating instructions when you pass the
product on to third parties.
1.3 Personal Protective Equipment
The following minimum Personal Protective Equipment (PPE) is
recommended when interacting with Nuaire product:
•
Protective Steel Toed Shoes -
when handling heavy objects.
•
Full Finger Gloves (Marigold PU800 or equivalent) -
when
handling sheet metal components.
•
Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent)
- when conducting light work on the unit requiring tactile
dexterity.
•
Safety Glasses
- when conducting any cleaning/cutting operation
or exchanging filters.
•
Reusable Half Mask Respirators
- when replacing filters which
have been in contact with normal room or environmental air.
Nuaire would always recommend a site specific risk assessment by a
competent person to determine if any additional PPE is required.
2.0 INTRODUCTION
Nuaire’s MRXBOX-AV4 is designed for use with MRXBOXAB-ECO4
MVHR units. The product offers a method of installation that isolates
the unit from the structure of the property and accommodates both
wall and floor mounting.
3.0 MECHANICAL INSTALLATION
Installation must be carried out by competent personnel in
accordance with the appropriate authority and conforming to all
statutory governing regulations.
Please note a clear working space is required around the installed
MRXBOXAB-ECO4 unit to allow the cover to be removed and provide
sufficient access for maintenance such as filter change. Please allow a
minimum of 480mm in front of the unit.
The hanging brackets of the MVHR unit and any ancillary silencer are
redundant when fitting the MRXBOX-AV4 and should not be used.
The fan must be installed indoors, on a suitable wall away from direct
sources of frost, heat, water spray or moisture generation.
For specific installation requirements of the MVHR unit to be installed
please refer to the installation and maintenance guide supplied with
the unit, the document covers additional items including access
requirements, airflow configurations, condensate drainage, electrical
connection and maintenance requirements that may influence the
location the MRXBOX-AV4 is to be installed.
Care must be taken to ensure the unit is installed true in all three
dimensions; failure to do so may result in overflow from the
internal condensation drip tray. To allow the anti-vibration mounts
to operate effectively no part of the MVHR unit should be in direct
contact with the building structure including any boxing in of the
duct connections, the only component of the assembly that should
be in contact is the mounting bracket.
3.1 Installation Procedure
All items referenced below including relevant fixings are supplied with
the MRXBOX-AV4, the exception being the fixings to secure the wall
brackets and the frame/plinth for floor mounting as these are specific
for the individual installation.
Fit 4x Anti-vibration (AV) mounts to the base of the MVHR using 8x
M8 screws pre-fitted in the base panel. If AV mounts are not required
skip the above step and proceed to Section 3.3 on page 2 "Wall
Mounting" to see how the MVHR unit can be secured direct to the
angle brackets)
If any Ecosmart products are to be used the connection to the