NuAire MEV-DC2 Installation And Maintenance Download Page 1

1.0 Introduction

Nuaire's MEV-DC2 units are designed to provide

continuous mechanical extract ventilation to homes

in accordance with Part F of the Building Regulation

2010 and BRE digest 398.

Coding/description is as follows:

MEV-DC2 Single fan unit.

The case is constructed in grey /blue ABS plastic. The full

length access cover which is located on the underside of 

the unit, on the opposite side to the mounting bracket, is

retained by four

1

⁄ 4

turn fasteners.

2.0 Installation

Installation must be carried out by competent personnel 

in accordance with the appropriate authority and 

conforming to all statutory and governing regulations.

The fan must be fitted indoors, away from sources of water

spray or steam generation. The fan can be installed at any

angle using the integral mounting bracket supplied (figure 2).

It is assumed that a solid non-reverberant mounting position

has been selected and the electrical mains wiring and any

optional control wires have been made ready.

It is also assumed that compatible ductwork is already

installed and ready to be connected to the 125mm dia.

discharge and inlet spigot.

Note: the unit is not fitted with a backdraught shutter. (When

using the continuous background vent facility a backdraught

shutter is not needed). However a backdraught shutter is

available from Nuaire if required.

An integral fixing bracket with a single bolt fixing allows easy

mounting and removal of the unit when necessary. The unit is

supplied with a 125mm dia. discharge and inlet spigot for 

fitting during installation.

2.1 Unit fixing

The integral mounting bracket supplied can be offered up to

position, the fixing points marked through and the bracket

installed with 4 screws by others. (See figure 2).

Offer the unit into position and locate the bracket into the

slots in the case before fixing with the single bracket fixing

screw.

As supplied the unit is fitted with:

5 off blanking plates (Do not remove)

2 off 125mm diameter spigots

Please note a clear space of at least 470 x 320mm is

required to allow the cover to be removed and provide 

sufficient access for maintenance.

The fan is designed to be wired direct to the mains supply

through a fused spur isolator (by others) and run 

continuously in the 

Normal

mode (which is the low speed,

background or trickle ventilation setting) with occasional

Boost

airflow (high speed setting) as and when required.

The unit is provided with adjustment for the low speed 

(Normal)

and high speed 

(Boost)

ventilation rate as required.

1

27. 04. 18. Leaflet Number 671559

 

Figure 1. 

MEV-DC2

Continuous Mechanical Extract 

Ventilation Units

Installation and Maintenance

Figure 2.

Fixing screw

hole.

Bracket tongues

engage with casing

slots, then unit

rotated up to 

align with fixing 

screw hole.

2 rubber cable 

entry grommets

either side of casing

for external wiring.

The EMC Directive 

2014/30/EU

The Low Voltage 

Directive 

2014/35/EU

Exhaust air from 

kitchen, bathroom 

and on-suite to 

outside via air brick.

Extract air from 

kitchen via

Air Valve mounted

in ceiling.

Top of ceiling void.

Nuaire MEVDC2 unit mounted

on the ceiling using an integral

mounting bracket.

Extract air from 

bathroom via

Air Valve mounted

in ceiling.

Extract air from 

on-suite via

Air Valve mounted

in ceiling.

Figure 3. Typical installation.

Nuaire: A Trading Division of Polypipe Limited  

Western Industrial Estate

 

Caerphilly  United Kingdom  CF83 1NA  

T: 029 2088 5911  F: 029 2088 7033  E: info@nuaire.co.uk  W: www.nuaire.co.uk

Summary of Contents for MEV-DC2

Page 1: ... position the fixing points marked through and the bracket installed with 4 screws by others See figure 2 Offer the unit into position and locate the bracket into the slots in the case before fixing with the single bracket fixing screw As supplied the unit is fitted with 5 off blanking plates Do not remove 2 off 125mm diameter spigots Please note a clear space of at least 470 x 320mm is required t...

Page 2: ...crew unit fixing 80 Do not use 125 dia 125 dia Alternative spigot positions 3 0 Dimensions Figure 4 Dimensions in mm Unit serving Kitchen and Bathroom Unit serving Bathroom only SL L N Optional lamp L N Fuse 2A Mains 230V 50Hz 3 Pole isolator Fan unit Remote light switch SL L N Fan unit 3 Pole isolator Room light L N Fuse 2A Mains 230V 50Hz Kitchen switch Light switch Double pole 4 0 Electrical Wi...

Page 3: ...are inspected and cleaned every year 7 0 Cleaning Remove covers and carefully clean out interiors as necessary Check for damage and security of components Refit covers 8 0 Replacement of Parts Should any component need replacing Nuaire keep extensive stocks for quick delivery Ensure that the unit is electrically isolated before carrying out any work When ordering spare parts please quote the seria...

Page 4: ...of the equipment must comply with the requirements of the relevant local electrical safety regulations 5 3 For EMC all control and sensor cables should not be placed within 50mm or on the same metal cable tray as 230V switched live lighting or power cables and any cables not intended for use with this product 6 0 COMMISSIONING REQUIREMENTS 6 1 General pre commissioning checks relevant to safe oper...