NuAire EST 19H-R Installation And Maintenance Manual Download Page 1

1

EST 19H & 20H

3ph 

Run & Standby, Roof & 

Plantroom Twinfans

Installation and Maintenance

 

Figure 1.  EST*-X  Plantroom/roof mounted in line unit.

Figure 2.  EST*-R  Roof mounted end inlet, side discharge unit.

Introduction

The Nuaire EST Twinfan Belt Drive range consists of the 

following units

EST-X (Duct Mounted, Plantroom/Roof) in line unit.

EST-R (Roof Mounted, end inlet) side discharge unit*. 

EST-B (Roof Mounted bottom inlet) side discharge unit*.

Units are rectangular in section. The casing is manufactured

from heavy gauge ‘Aluzinc’ aluminium-zinc coated mild steel.

A full size internally lined access panel is fitted to the top face

and this panel is fully detachable for inspection purposes. 

The motor plate and frames are supported on the base by

resilient mountings allowing the fan unit to be operated without

the need for separate anti vibration fan case mountings. 

 

Suitable for operation in ambient temperatures up to 40

o

C. 

Handling

Always handle the units carefully to avoid damage and distortion.

 

Eyebolts are provided on all units for lifting purposes. 
If mechanical aids are used to lift the unit, spreaders should be

 

employed and positioned so as to prevent the slings, webbing

 

etc. making contact with the casing. 

Figure 3.  Bottom inlet unit.

A

B

Removable 
top panel

F

E

Control module
located internally

Commissioning box

Bottom inlet

C

Opposed outlet grilles

A

50mm

B

F

C

E  

Rectangular spigots 
size EST20

H

)

Circular spigots 
size EST19

H

)

D dia

Removable top panel

Commissioning 
box

EST-X

EST-R

EST-B

Unit

A

B

C

D dia

E

F

EST 19H-X

1430

1635

840

630

-

-

EST 

20H-X

2030

2313

1183

-

1200

700

Table 1. Dimensions (mm)

For unit weights see page 4

A

B

Removable 
top panel

Opposed outlet grilles

External 
commissioning box.

D dia

Control module
located internally

C

Table 3.   Dimensions (mm)

For unit weights see page 4

Unit

A

B

C

D dia

EST 19H-R

1430

1635

840

630

Table 2. Dimensions (mm)

For unit weights see page 4

28. 06. 17. Leaflet Number 671845

Rect Spigot

Unit

A

B

C

E

F

EST 19H-B

1430

1635

840

889

381

* larger units have end discharge

Table 4.   Dimensions (mm)

For unit weights see page 4

Rect Spigot

Unit

A

B

C

E

F

EST 20H-B

2030

2313

1183 1200

700

EST 20H-R

2030

2313

1183

1200

700

Louvred
end outlet

Bottom rectangular inlet 
spigot Code: EST*-B

F

E

B

A

C

F

E

End inlet rectangular spigot Code: EST*-R

Commissioning box

EST-B/R larger units

Figure 4.  Bottom inlet unit.

The EMC Directive 
20

1

4/

30

/E

U

  

The Low Voltage 
Directive 
20

14

/

3

5/E

U

Nuaire: A Trading Division of Polypipe Limited  

Western Industrial Estate

 

Caerphilly  United Kingdom  CF83 1NA  

T: 029 2088 5911  F: 029 2088 7033  E: [email protected]  W: www.nuaire.co.uk

Summary of Contents for EST 19H-R

Page 1: ...h the casing Figure 3 Bottom inlet unit A B Removable top panel F E Control module located internally Commissioning box Bottom inlet C Opposed outlet grilles A 50mm B F C E Rectangular spigots size ES...

Page 2: ...try must be properly sealed NOTE on bottom inlet units the electrical cabling may be routed up through the bottom inlet spigot Upstand Details Details of roof opening dimensions etc required and basic...

Page 3: ...in table 7 are nominal Run currents will be exceeded if the unit is operated with its cover removed The unit must not run for more than 2 minutes in this condition Note Please see Electrical Sound an...

Page 4: ...t supplied It is available from R S Components Part No 403 875 or Farnell Part No 963 021 The system s response to a 0 10V dc BMS signal is given in the table below Note the BMS signal will override a...

Page 5: ...ple to run the fan with a temperature sensor connect a link across L to SL enabling signal and connect a temperature sensor in one of the sockets labelled NET The fan will now adjust its speed accordi...

Page 6: ...e before commencing any work on the unit Installation and Maintenance ECOSMART EST 19H 20H Roof Plantroom Twinfans 6 28 06 17 Leaflet Number 671845 Fan Unit Maintenance Intervals The first maintenance...

Page 7: ...uirements should be noted 5 1 Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting the...

Reviews: