ESH Ecosmart Heater

The Ecosmart Heater should only be used as a 

supplementry heater in conjunction with a 

Ecosmart supply fan with integral electric heater. 

It must not be used with any other fans.

The heater is a 3kW single phase unit that requires an 

independent 230V mains supply to the top mounted 

terminal box and is supplied with a pre-plugged 10m length

of communications cable. 

This heater will provide additional heat where the desired

temperature cannot be achieved by the supply fan’s integral

heater alone.

Note: the air velocity through the heater section must be

1.5m/s or greater.

Installing the Heater

The Heater must be fitted indoors, away from any water

spray or source of steam.

The heater is installed into the ductwork (by others) using

the fast clamps at the downstream side of the supply fan.

Larger, heavier units should be adequately supported.

ESH Ecosmart 
Heaters 

Installation Guide

Supply unit with

heater

Temperature sensor

(see locating 

temperature probe

overleaf

Figure 2. Ecosmart heater dimensions.

Mains supply 

terminals

SELV cable

Figure 1. ESH Ecosmart heater typical system application.

Heater 

Matched 

D

L

Unit

Unit

Spigot dia. mm

length

ESH2 

ESS2-E

150

400

ESH3

ESS3-E

200

400

ESH4

ESS4-E

250

400

ESH5

ESS5-E

315

400

*Dia. D suits matched Ecosmart unit.

Ecosmart heater