NuAire ES-MEV Hints & Tips Download Page 1

0.01

1

ES-MEV 

- Hints & Tips

GUIDANCE NOTES 10

Technical Support Dept.

T. 02920 858585  F. 02920 858586

Leaflet Number 671414 January 2010

Calibration

Status

30

0

60

Run-on

(mins)

50

10

90

Max

Airflow

(l/s)

50

10

90

Min

Airflow

(l/s)

TEST BUTTON

SL RUN ON

MAX SPEED

ADJUST

MIN SPEED

ADJUST

LED

continued overleaf.

Nuaire Group

Western Industrial Estate Caerphilly  United Kingdom CF83 1NA

Telephone: 029 2085 8200   Facsimile: 029 2088 7033  Email: [email protected]   www.nuaire.co.uk

N

L

SL

Do not use

To OPUS-SPD 
speed control

Internal 
humidity adj.

To remote  
fail indicator 
ES-MEV-AVI

Calibration

Status

30

0

60

Run-on 

(mins)

50

10

90

Max  

Airflow 

(l/s)

50

10

90

Min  

Airflow 

(l/s)

     

  LVT       NET     TR

1.0. On Installation

Follow the installation and maintenance document
671266 for ES-MEV, paying particular attention to;

1.1. 

The chosen location for installation.

a).  Mounting the unit using the integral mounting 

bracket supplied.

b).

Mount the unit on a non reverberant surface.

c).

The unit can be mounted at any angle.

d).

Make sure that when the unit is mounted
sufficient space is left around the unit for
maintenance and the fixing of the ducting.

e).

If installed with flexible duct special care/
consideration should be made to prevent the 
duct being closed off, cracked or twisted, 
introducing a high resistance on the system.

1.2. 

Electrical.

a).

Pay particular attention to electrical 
connections referring to the I&M for correct
method.

b).  Isolation of the unit and any switched live 

circuits should be achieved through the same 
isolator.

230V Switched live

1.3 Setting to work

When initially powered the ES-MEV will self 
calibrate, it will try to achieve the duties set by 
the MAX and MIN set points.

The calibration process can take around 2 minutes
and is as follows:

Unit runs to full speed. (Faster than the max 
set point).

The unit will slow down and eventually stop.

A 10 second wait.

It will restart and run at ¼ speed.

The unit then settles to the MIN speed.

If, during this process the red LED should illuminate,
ensure there are no switched live or boost signals
present. 

Upon completion of the calibration process apply a
switched live (SL), the fan speed and duty should
increase to that of the MAX set point.

When testing a system

a).

The ‘dial a duty’ set points should be positioned
with the MAX at MAX and MIN at MIN, i.e. 
giving the widest possible speed control range. 

b).

On an existing installation it is important to 
observe and note these duty positions should 
it be necessary to return to them later.

c).

The SL run on should be set to minimum to 
reduce the run on time during test, it is 
important to note the position set should it be 
necessary to return to it later. 

Circuit board connections.