NuAire ECOSMART TWINFAN Series Installation And Maintenance Manual Download Page 1

Nuaire Limited

Western Industrial Estate  Caerphilly  United Kingdom  CF83 1NA  

T: 029 2085 8400  F: 029 2085 8444  E: [email protected]  W: www.nuaire.co.uk

1

Introduction

Units are rectangular in section and consist of three basic

designs.

Full size access panels are fitted to the top of the units and 

are fully detachable for inspection and connection purposes.

The models are coded as follows:

EST-X (External/Internal Duct Mounted) in line unit.

EST-R (Roof Mounted, end inlet) side discharge unit.

EST-B (Roof Mounted bottom inlet) side discharge unit.

EST-X

units are rectangular in section and have circular rigid

spigots at each end. 

EST-R

units are rectangular in section and are supplied with 

a circular end spigot and two opposed side discharge grilles.

EST-B

units are rectangular in section and have a rectangular

bottom spigot and two opposed side discharge grilles. 

Handling

Always handle the units carefully to avoid damage and 

distortion. If mechanical aids are used to lift the unit, spreaders

should be employed and positioned so as to prevent the slings,

webbing etc. making contact with the casing.

Installation

Installers - please note that Installation must be carried 

out by competent personnel in accordance with the 

appropriate authority and conforming to all statutory and 

governing regulations e.g. I.E.E, CIBSE, COHSE.

EST-X/R/B units are suitable for internal or external use.  

All units can be installed at any angle up to 60

o

however, 

on a

sloping roof the unit must be blowing upwards

toward the

roof ridge to ensure correct backdraught shutter operation.

Units should always be positioned with sufficient space to

allow removal of the access cover and subsequent removal

of fan and motor assemblies etc.

Whether internally or externally mounted, the method of fixing

to the roof is the responsibility of the installer.

All units have a bottom skirt to allow for fixing directly onto 

a suitably sized curb or builders upstand. Nuaire can supply a

matching prefabricated curb for these units.  Details of curbs

and dimensions for a suitable external concrete upstand are

shown on page 2. 

Ductwork connections must be airtight to prevent any loss of

performance. 

Table 1. EST-X Dimensions (mm) 

Weight

Code

A

B

C

D dia.

(kg)

EST1-X

705

505

355

125

22

EST2-X

875

720

400

200

35

EST3-X

970

720

485

200

50

EST4-X

1165

980

575

250

72

EST5-X

1165

980

575

400

75

EST6-X

1165

980

575

400

86

EST9-X

1495

1125

710

500

162

Weight

Unit

A

B

C

D dia.

E

F

(kg)

EST1-R 

705

505

355

125

22

EST1-B 

705

505

355

-

76

152

22

EST2-R 

875

720

400

200

-

-

35

EST2-B 

875

720

400

-

127

229

35

EST3-R 

970

720

485

200

-

-

45

EST3-B 

970

720

485

-

127

229

45

EST4-R

1165

980

575

250

-

-

72

EST4-B

1165

980

575

-

152

305

72

EST5-R

1165

980

575

400

-

-

75

EST5-B

1165

980

575

-

229

457

75

EST6-R

1165  

980

575

400

-

-

86

EST6-B

1165  

980

575

-

229

457

86

EST9-R

1495

1125

710

500

-

-

162

EST9-B

1495

1125

710

-

304

762

162

External

Commissioning box

D

C

A

B

Removable 

top panel

Control module

located internally

EST-X

EST-R & EST-B

A

B

Removable 

top panel

Commissioning box

Opposed

outlet

grille

Circular inlet spigot  

on end of unit  

Code: EST*-R

D

E

F

Control module

located internally

C

Rectangular bottom  

inlet spigot EST*- B only

16. 06. 15. Leaflet Number 671142

Figure 1.  EST-X unit.

Figure 2.  EST-R/B  units.

ECOSMART TWINFANS

(EST-X/R/B)

1 phase, Direct Drive, 

Run & Standby

For External, 

Roof Mounted and Internal use

Installation and Maintenance

The EMC Directive 

2014/30/EU 

The Low Voltage 

directive 

2014/35/EU

Table 2. EST-R / B Dimensions (mm) 

In High humidity applications above 90% 

trickle ventilation is recommended. 

Summary of Contents for ECOSMART TWINFAN Series

Page 1: ...uent removal of fan and motor assemblies etc Whether internally or externally mounted the method of fixing to the roof is the responsibility of the installer All units have a bottom skirt to allow for...

Page 2: ...h The fan casings have an inside skirt depth of 60mm or in the case of the largest size units only 50mm It is recommended that the units are mounted upon a suitable curb or upstand which has a minimum...

Page 3: ...e total data cable length used in any system must be less than 1000m Keep the number of cable joints to a minimum to ensure the best data transmission efficiency between devices e Maximum number of de...

Page 4: ...10V dc BMS signal is given in the following table Note the BMS signal will override any sensors and user control connected in the system The voltage tolerance is _ 125mV and is measured at the fans te...

Page 5: ...freely Refit the assemblies to the unit see Replacement of Parts then replace the access cover If Nuaire controls and or remote indicators are fitted remove the cover and carefully clean out the inte...

Page 6: ...Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate...