Constant Pressure 
Motorised Grille Damper
Type NRG

Installation and Maintenance

Introduction

The motorised damper is manufactured from ABS plastic

and designed for installation with NUAIRE’s range of

Ecosmart Constant Pressure Variable Volume extract fans.

The NRG incorporates a damper that is motorised upon

activation/deactivation of the integral PIR. 

Principle features are:

Integrated PIR with pre set nominal fifteen minute

overrun timer

12V operating via a 12/230V transformer supplied

as standard.

The damper is ‘pegged’ so as to prevent full closure,

thereby ensuring continuous trickle ventilation when

the constant pressure fan is operating

There are four fully open positions to be manually

set at the required boost ventilation rate at

commissioning stage.

Handling

Handle the unit with care to avoid damage and distortion to

moving parts.

Installation

The installation must be carried out by suitably qualified

and competent personnel in accordance with appropriate

authority and in conformance with all statutory and 

governing regulations i.e. IEE CIBSE COHSE HVCA etc.

Figure 1. Dimensional Detail

Mechanical Installation

The grille is suitable for internal installation only, mounting

in any attitude and can be installed within the splash zone.

The grille has a 125mm diameter discharge spigot and is a

‘push fit’ to corresponding ductwork, its held in position 

by the compression seal attached to the spigot. 

Before offering to the ductwork complete the electrical 

connection.

Electrical  Installation

Position the transformer in the ceiling or service void 

allowing for future access, connect to a 230V supply via a

spur fused at 1A. Connect the 12V transformer output to the

connection leads of the grille.

Figure 3. Wiring detail

1

15

. 0

5.

 17. Leaflet Number 671279

Figure 2. Performance Detail

Lw

Position 1

Position 2

Position 3

Position 4

70Pa 

25.1

21.6

-

23

100Pa

30

30.3

32.2

33.3

130Pa

33.5

32.8

36

37.1

150Pa

37.1

37.3

-

38.6

Acoustic Information

Connector Block (by others)

Figure 4. Transformer dimensions

The EMC Directive 

2014/30/EU 

 

The Low Voltage 
directive 

2014/35/EU