NuAire dMEV+H Installation Manual Download Page 1

1.0 Introduction

The dMEV+H is a 2 speed axial extract fan has been designed for
continuous ventilation for kitchens or wet rooms and should be
installed using 100mm dia. ducting.

Speed settings are fixed at either Low Speed and Low Boost or
High Speed and High Boost (See Section 9.0 for Details).

As a default, the fan is set to achieve low speed (6 l/s – wet rooms)
to adjust to high speed (8 l/s - kitchen) refer to section 9.0.

2.0 Handling

Always handle the the fan carefully to avoid damage and distortion.

4.0 Spacer installation (if required)

3.0 Installation

The installation must be carried out by competent personnel in

 

accordance with the appropriate authority and conforming to all

 

statutory and governing regulations i.e. IEE, CIBSE, CCHSE, HVCA etc.

The unit is for indoor use only, and is suitable for through wall and

 

ceiling installation. Mount on a secure, vibration free surface away

 

from any direct source of heat and areas where it would be subjected

 

to water spray. 

The maximum permissible ambient temperature is 50

°

C.

dMEV+H Box Contents

Fan unit (Including 2 part inlet grille and 2 fixing screws), wiring

 

grommets (2 off), a cable clamp c/w screws and spacer.

dMEV

+

H

Decentralised Mechanical Extract Ventilation 
2 Speed Axial Extract Fan with Humidity Enabler

Installation Guide

The EMC Directive 

2014/30/EU  

The Low Voltage 
Directive 

2014/35/EU

10

. 0

5

. 17. Leaflet Number 671665

1

Figure 1.

DMEVH & DMEV+H 

ONLY

Snap off top lug (highlighted in grey)

(eight lugs in total, two in each corner) 

 

Corner post once top lugs

have been removed

Fig. 1 Spacer Installation

Having established the mounting position

for the unit, mark the centres of duct hole and four fixing points
using the template provided on page 5. 

Core cut the centre duct hole, drill and plug mounting holes. 

When using surface mounted cabling select the most appropriate
cable entry position and carefully trim out the inner and outer cable
cut-outs. 

Secure spacer to the wall / ceiling (fixings supplied by others). Note:
use wood screws not countersink screws to avoid distorting the skirt. 

Chased in Cable:

Feed the cable through the spacer to pass through back plate for
when installing fan. 

Wire outlet
position