CM-XBOX-INLINE

Cooling module for use with MVHR Units

Installation and Maintenance

The EMC Directive

 

2014/30/EU

The Low Voltage 
Directive

2014/35/EU

1.0 SAFETY INFORMATION

The provision of the electrical supply and the connection of the unit to the mains 
must be carried out by a qualified electrician. Ensure that the mains supply (Voltage, 
Frequency and Phase) complies with the rating label.

Isolate from power supply before removing any covers. During installation / 
maintenance ensure all covers are fitted before switching on the mains supply.

All-pole disconnection from the mains as shown in the wiring diagram must be 
incorporated within the fixed wiring and shall have a minimum contact separation of 
3mm in accordance with latest edition of the wiring regulations.

This unit must be earthed.

Ducting must be securely fixed with screws to the spigot to prevent access to live 
parts. 

If the supply cord is damaged, it must be replaced by its service agent or similarly 
qualified persons in order to avoid a hazard. 

When installing the unit, take care not to damage electrical or other hidden 
components – do not drill the unit casing. 

Precautions must be taken to avoid the back-flow of gases into the room from the 
open flue of gas or other fuel-burning appliances. 

The unit must be installed indoors, and away from direct sources of frost, heat and 
water spray or moisture generation. Ambient temperature range -5 to 40 deg C. 

The cooling unit is an electro-mechanical device that contains and uses R407C 
refrigerant. The unit provides cooling in the range of 0.4 to 1.4 kW. The weight of the  
R407C refrigerant is 0.63Kg.

This appliance should not be used by children or persons with reduced physical, 
sensory or mental capabilities or lack of experience and knowledge, unless they 
have been given supervision or instruction concerning the safe use of the appliance 
by a person responsible for their safety. Children shall not play with the appliance. 
Cleaning and user maintenance shall not be carried out by children. This unit contains 
live electrical components, moving parts and refrigerant under pressure. Always site 
out of reach of children and protect from vandalism and accidental damage. 

Summary of Contents for CM-XBOX-INLINE

Page 1: ...fied persons in order to avoid a hazard When installing the unit take care not to damage electrical or other hidden components do not drill the unit casing Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel burning appliances The unit must be installed indoors and away from direct sources of frost heat and water spray or moisture generat...

Page 2: ... outer fixing holes on the unit are accessible Note The unit must be installed in an upright position as shown for the condensate drain and for compliance with safety regulations relating to IP protection for water drip ingress 2 2 Condensate Drain Installation Unit comes complete with external condensate drain pipe of 15 mm diameter positioned 20 mm up from the base and 80mm back from the supply ...

Page 3: ...pply air temperature is critical to ensure good cooling distribution and to avoid condensation forming on supply terminals MVHR duty in cooling mode must be sufficient to avoid Over cooling If supplying to habitable rooms through Linear Slot Diffusers 12 C is the recommended minimum supply air temperature If supply to habitable rooms is by air valve then 14 C is the recommended minimum supply air ...

Page 4: ...ng 7 0 ELECTRICAL INSTALLATION 7 1 Wiring 7 2 Electrical Details Voltage 230V 1ph 50Hz Running Current 2 8 Amp Locked Rotor Current 15 Amp NOTE This unit must be earthed B A MVHR SUPPLY CORD FROM MVHR MAINS 230V 50Hz N L L LIGHTING CIRCUIT CM XBOX INLINE COOLING MODULE THERMOSTAT CONTROL CM THERM CONTROL B B A B MVHR PURGE COOLING MODULE ENABLE FROM CM THERM CONTROL A MVHR BOOST CONTROLLED FROM LI...

Page 5: ...pressor failure a sample of oil should be removed from the compressor by draining through the discharge port This sample should be tested using a proprietary acid test kit to determine if the failure has resulted in a burn out If the oil is clean a new compressor can be fitted immediately In the event of a burn out the system will need cleaning In the absence of any approved flushing agents a burn...

Reviews: