The unit must remain switched on at all times to maintain

ventilation within the dwelling. Turning the unit off will

cause long term damage to the unit and building fabric.

This appliance is not intended for use by persons 

(including children) with reduced physical, sensory or

mental capabilities, or lack of experience and knowledge,

unless they have been given supervision or instruction

concerning the use of the appliance by a person for their

safety. Children should be supervised so that they do not

play with the appliance.

MRXBOX95AB-WM2QA11179

Mechanical Ventilation Unit with Heat Recovery 

& Summer Bypass for Wall Mounting

Installation and Maintenance

1.0 Introduction

MRXBOX95AB-WM2QA11179 wall mounted unit is designed to 

provide mechanical supply and extract ventilation with heat

recovery and incorporates an integral automatic summer

bypass.

The unit is fitted with two independent fans. Each fan has full

speed control for background and boost ventilation rates. 

To recover heat from the extract air the heat exchanger block 

is utilised. The heat exchanger can recover up to 95% of the 

normally wasted heat.

Integral automatic summer bypass 

- The bypass damper

shall open automatically via a wax actuator allowing the air to

bypass the heat exchanger to deliver fresh filtered air during

the warmer months.

2.0 Installation

Installation must be carried out by competent personnel in

accordance with the appropriate authority and conforming 

to all statutory governing regulations. All mains wiring must 

be in accordance with the current I.E.E. Regulations, or the

appropriate standards. Ensure that the mains supply 

(Voltage, Frequency and Phase) complies with the rating label. 

Please note a clear working space is required around the

installed unit to allow the cover to be removed and provide 

sufficient access for maintenance such as filter change.

Please allow a minimum of 350mm in front of the unit.

The fan must be installed indoors, on a suitable wall away

from direct sources of frost, heat, water spray or moisture

generation. For a vibration-free result the unit must be 

mounted to a solid wall.

Note: Care must be taken to ensure the unit is installed true

in all 3 dimensions. Failure to do so may result in overflow

from the internal condensation drip tray.

For installation details of MRXBOX95AB-WM2 and 

ancillary MRXBOX-AB-WM2 refer to project specific 

documentation agreed as part of contract.

Nuaire Limited

Western Industrial Estate  Caerphilly  United Kingdom  CF83 1NA  

T: 029 2085 8400  F: 029 2085 8444  E: [email protected]  W: www.nuaire.co.uk

1

05. 09. 14. Leaflet Number 671672

The EMC Directive 

2004/108/EC  

The Low Voltage 

Directive 

2006/95/EC

Extract air 

from house

Intake air 

from outside

Exhaust air 

from house

to outside

Supply air 

to house

Figure 1. Airflow through unit.

Summary of Contents for MRXBOX95AB-WM2QA11179

Page 1: ...ng the warmer months 2 0 Installation Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory governing regulations All mai...

Page 2: ...nded Ideally 150mm diameter or 204 x 60mm rectangular ducting should be used Refer to dwelling design drawing figure 7a and 7b on page 4 for further information Ducting joints must be sealed with sili...

Page 3: ...boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 for minimum high rate n the minimum air supply ra...

Page 4: ...Minimum 300mm Air supply to lounge via Air Valve Part no VS125 in ceilings Extract air from kitchen bathroom via Air Valve Part no VS125 in ceilings Air supply to bedrooms via Air Valve Part no VS125...

Page 5: ...0Hz Room lights Light switches Double Pole N L 3 Pole isolator 3 Pole isolator Kitchen switch Kitchen switch Blue Brown Black Optional summer boost switch Supply cord from unit Green yellow Blue Brown...

Page 6: ...cked in place to prevent further adjustment 6 Once commissioned the home owner tenant should be informed that the unit should not be adjusted as it will have a detrimental effect on the indoor air qua...

Page 7: ...ated before carrying out any work Note The supply cable must be replaced by an electrically competent person When ordering spare parts please quote the serial number of the unit and the ARC number of...

Page 8: ...have no adverse effect on the fan The speed will return to normal once the interference has subsided 5 0 INSTALLATION REQUIREMENTS In addition to the particular requirements given for the individual...

Page 9: ...ings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Custome...

Page 10: ...r to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow an...

Page 11: ...y unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Hav...

Page 12: ...or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been pro...

Page 13: ...tion grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Se...

Page 14: ...e customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised...

Reviews: