3.3. Wiring
3.3.4. Ground Connection
2
2
3
3
t
t
y
y
p
p
e
e
2
2
5
5
t
t
y
y
p
p
e
e
Figure 3-6: Wiring example in case of a Driver Unit with TB2 for thermal sensor
*1
*1
*1: Connect at one point.
*1
*1
Resolver
Motor
Driver Unit
AC Power
Ground earth
Class 3
or better
FG
Main power
TB1
Control
power
CN5
Master controller
• Controller (pulse train output)
• Sequencer
24 VAC
Power source
CN4
CN2
CN3
*1
*1
Directly ground
the Motor base
using bolts
*1
ELB1
MC1
I/O signal
+ 24 V
COM
DRDY +
DRDY -
RY1
NF1
I/O signal
+ 24 V
COM
+ 24 V
GND
ELB1
:
Short circuit breaker
CB1 :Non fuse breaker
NF1
:
Noise filter
MC1
:
Magnetic switch
RY1
:
Relay
SW1
:
Main power switch ON
SW2
:
Main power switch OFF
NF
15
2
SW1 SW2
MC1
MC1
RY1
CB1
Thermal sensor
(Normally closed)
TB2
S1
S2
!
Caution : We recommend the following noise filter for an measures against EMC
Directive.
à
PN2070-10/06 (Schaffner) equivalent
(Use a breaker compatible with the European Safety Directives.)
!
Caution : Provide a circuit to shutdown the main power by an output of an alarm.
à
When an alarm is given, #2 and #15 of CN2 for DRDY (Driver Unit ready) outputs
open.
l
Alarm of “Main AC Line Trouble” will be given when the main power is turned off while the
servo is on. This alarm cannot be cleared until the control power is turned on again.
(Refer to “7-1.1. Servo on.”)