8.Maintenance
Trouble shooting when alarm activated
8-15
■
Alarm Code 56 (Main Circuit Power Device Overheat)
Status at the time of alarm
Cause
1
2
3
4
Issued when control power is turned ON.
✔
✔
✔
Issued at servo input.
✔
✔
✔
Issued while starting and stopping the motor.
✔
✔
✔
Issued after operation for some time.
✔
✔
✔
✔
◆
Corrective actions
Cause
Investigation and corrective actions
1
■
U/V/W-phase of driver is short
circuited due to the wiring in driver
and motor. Also, U/V/W-phases are
grounded in the earth.
■
Check wiring and replace if necessary.
2
■
Short circuit or fault in U/V/W phases
on motor side.
■
Replace the motor.
3
■
Defect in internal circuit of driver.
■
Replace the driver.
4
■
Ambient temperature is high.
■
Confirm that the temperature of the
control board (ambient temperature of
the driver) does not exceed 55°C. If in
excess of 55°C, check the installation
method of the driver, and confirm that
the cooling temperature of the control
board is set to below 55°C.
■
Alarm Code 61 (Over-Voltage)
Status at the time of alarm
Cause
1
2
3
4
Issued when power supply control is turned ON.
✔
Issued when power supply of main circuit is turned ON.
✔
✔
Issued while starting and stopping the motor.
✔
✔
✔
◆
Corrective actions
Cause
Investigation and corrective actions
1
■
Defect in internal circuit of driver.
■
Replace the driver.
2
■
The power supply voltage of main
circuit is out of the specification.
■
Reduce the power supply voltage to
within the specified range.
3
■
Excessive load inertia moment.
■
Reduce the load inertia moment to within
the specified range.
4
■
Incorrect wiring for regeneration
resistance.
■
Built-in regeneration circuit is not
functioning.
■
Wire the regeneration resistance
correctly.
■
While using the external regenerative
resistance, check the wiring and
resistance value.
■
Replace the driver if any abnormality
occurs.