5.Operation
Group 4 Gain switching control/ Vibration suppressor frequency switching settings
5-45
ID
Contents
04
Velocity Loop Integral Time Constant 2
[TVI2]
Setting range
Unit
Standard value
0.3 to 1000.0
ms
20.0
14
Velocity Loop Integral Time Constant 3
[TVI3]
Setting range
Unit
Standard value
0.3 to 1000.0
ms
20.0
24
Velocity Loop Integral Time Constant 4
[TVI4]
Setting range
Unit
Standard value
0.3 to 1000.0
ms
20.0
■
Integral time constant for velocity controller. Select from gain switching function 1 and 2.
◆
This parameter is not covered by Auto-tuning result saving.
◆
This setting is valid when Velocity Loop Proportional Control Switching Function is
invalid.
◆
Integral time is invalid (proportional control) with the setting value 1000.0ms.
05
Load Inertia Moment Ratio 2
[JRAT2]
Setting range
Unit
Standard value
0 to 15000
%
100
15
Load Inertia Moment Ratio 3
[JRAT3]
Setting range
Unit
Standard value
0 to 15000
%
100
25
Load Inertia Moment Ratio 4
[JRAT4]
Setting range
Unit
Standard value
0 to 15000
%
100
■
Sets Inertia moment of load device to the motor inertia moment. Select from Gain switching
function 1 or 2.
◆
If this value matches the actual mechanical system, the setting value corresponding to
Velocity Loop Proportional Gain (KVP2, KVP3, and KVP4) is response frequency of the
velocity control system.
◆
This parameter is not covered by Auto-Tuning Automatic Parameter Saving function.
◆
Setting value=J
L
/J
M
×100[%]
J
L
: Load inertia moment
J
M
: Motor inertia moment
06
Torque Command Filter 2
[TCFIL2]
Setting range
Unit
Standard value
1 to 4000
Hz
600
16
Torque Command Filter 3
[TCFIL3]
Setting range
Unit
Standard value
1 to 4000
%
600
26
Torque Command Filter 4
[TCFIL4]
Setting range
Unit
Standard value
1 to 4000
%
600
■
Low-pass filter to eliminate high frequency element included in torque command. Select from gain
switching function 1 or 2. Sets cutoff frequency.
◆
This parameter is not covered by Auto-tuning result saving.
◆
Setting range varies depending on the setting of system parameter ID00 Control Cycle.
(Torque command filter cannot be disabled.)
Control Cycle
Setting value
Cutoff frequency
00
Standard_Sampling
Standard Sampling
1 to 2000[Hz]
Setting value
2001 to
4000[Hz]
2000[Hz]
01
High-freq_Sampling
High Frequency Sampling
1 to 4000[Hz]