© Brüel & Kjær Vibro
● C107759.002 / V03
Page 15 of 22
Technical alterations reserved!
Brüel & Kjær Vibro
│
Instruction VCM-3 On-Site Commissioning
VCM-3 Homepage Commissioning
Procedure
EN
UNRESTRICTED DOCUMENT
4.4
Check bias voltages of sensors
Use the Commissioning Report feature to check the bias voltages of the connected sensors.
NOTE!
The Commissioning Report is only supported with an activated Factory Monitoring
Template, which is not to be exchanged with the Standard (Master) Monitoring
Template and/or the customized Monitoring Template created with the VCM-3 Editor
software.
View Commissioning Report
1
Select Commissioning Report from the VCM-3 Homepage menu
2
Inspect the report.
•
The bias voltages (Level) of CCS sensor shall be between 11 and 14 Volts
•
The bias voltages (Level) of the AS-247 MEMS sensor on Channel 11 and 12 (if present) shall
be between 1.5 and 3 Volt.
•
Put a piece of metal in front of the rotational speed sensor. It shall show approximately 25 V.
The 50/60Hz noise shall be in the mV range