Page 14 of 22
© Brüel & Kjær Vibro
● C107759.002 / V03
Technical alterations reserved!
EN
UNRESTRICTED DOCUMENT
4.3
Check the Operational Status
NOTE!
This page is only available on VCM-3 with installed firmware version 1.15 or higher.
How to inspect the Operational Status page
1
After login the Operational Status page is shown. This page gives an overview of the present status
of the VCM-3. As a general rule the status indicators in the red boxes must have the status as
shown on the screen shot. Otherwise there is a problem with the VCM-3.
The other status indicators are dependent upon the state of the commissioning procedure.
2
If the status indicators in the red boxes shows a different result, try to reboot the VCM-3 and
inspect the Operational Status page again.
1. Reboot the VCM-3 and check if the problem disappears. The reboot activates some repair
facilities.
2. If 1.) does not help then make an upgrade of the firmware. Refer to the procedure in On-site
Commissioning instruction C107759.002 EN: Appendix 2.
3. If 2.) does not help the VCM-3 has a fault. Exchange the VCM-3 with a spare unit.