Instruction VCM-3 On-Site Commissioning
Initial Power Up test
– Visual check
EN
UNRESTRICTED DOCUMENT
Device Status /
LED color
Explanation
Status: System
On
– Red. Watchdog about to reboot the VCM-3
Action:
1. If watchdog reboot does not help, make a manual reboot. The reboot
activates some repair facilities.
2. If 1) does not help, then make an upgrade of the firmware. Refer to
the procedure in Appendix 2.
3. If 2) does not help the VCM-3 or the running template has a fault. Try
changing to the factory template. If that solves the problem the
template must be replaced or updated. If the problem is present with
the factory template
– replace the unit..
Status: Template
On
– Red. Fatal template error
Action:
1. Reboot the VCM-3 and check if the problem disappears. The reboot
activates some repair facilities.
2. If 1) does not help then make an upgrade of the firmware. Refer to
the procedure in Appendix 2.
3. If 2) does not help the VCM-3 has a fault. You cannot complete the
commissioning procedure. Exchange the VCM-3 with a spare unit.
Status: Online
On
– Red. Either default gateway cannot be reached (but before) or network
has a configuration error. (Maybe the specified IP address is illegal)
Action:
1. Reboot the VCM-3 and check if the problem disappears. The reboot
activates some repair facilities.
2. If 1) does not help go to the Network configuration page and check.
Boot Status
On
– Red. Unit is off and power is within specification. Ready to be turned on.
Action:
1. Push the
Power Up/Down
button but only with a short push. If this
turns the
Boot Status
into green the VCM-3 is OK.
2. If 1) does not help then reboot the VCM-3 and check if the problem
disappears. The reboot activates some repair facilities.
3. If 2) does not help the VCM-3 has a fault. You cannot complete the
commissioning procedure. Exchange the VCM-3 with a spare unit.