6.5 How to Configure the Controller for Kits 11709 and 11710
Both heating and ventilation are required when using kits 11709 and 11710, and the default program in
the PLC comes preconfigured to handle the climate types for these kits. No modification of the PLC
program is necessary.
6.6 Advanced User Settings – PLC Control Algorithm
A few settings are available for advanced users who want to custom tailor the control algorithm of the
PLC.
Heater switch on time
Heater switch off time
Temperature threshold for switching on the heater
Temperature threshold for switching off the heater
Ventilator can be configured to run continuously in addition to the default 6AM to 8PM
Notes for Advanced Users:
Be careful when making adjustments to these settings as there is no master reset which can
restore the PLC to the original NRG factory settings! A programming key is required for
factory reset.
Adjustments to the default settings can significantly change the power required to run the
system. As a reference, the system runs on 12 Volts. The heater consumes 10 Watts and the
Ventilator consumes 8 Watts. NRG supplied battery capacity is 108 ampere hours (per battery)
and NRG designed the system to nominally have a 4 day reserve (4 days without PV power
input) for the specified target climate conditions. Be sure to account for these specifications
when making any changes to the control algorithm!
The following sub-sections describe how to make adjustments to these settings.
Note: The PLC needs to be in RUN mode in order to adjust these settings.
6.6.1 Heater switch on time
Press ESC. You should see the PLC home screen “NRG Systems”, press the up arrow once to enter the
heater switch time menu.