6 Settings
PCS-9785 Satellite Synchronized-Clock
6-12
Date: 2019-07-05
6.3.7 Internal Clock Operation Mode
If the operation mode of internal clock is "ON" (default) and there is no IRIG-B signal input, the
time synchronization source will be the internal clock. Then, if one of the two inputs has received
IRIG-B signal, the time source will be switched automatically. Additionally, the internal clock will be
synchronized every minute.
If the operation mode of internal clock is "OFF" and there is no IRIG-B signal input, there will be no
time synchronization output from this device.
Command format: CD
C
The command key word
D
Internal clock operation mode, 1: ON; 0: OFF
Example: C1 means the operation mode is ON.
Command format: C?
To query the current internal clock operation mode.
6.3.8 Input Channel Alarm Mode
The two IRIG-B signal inputs can be adopted together or separately. The input channel alarm
mode should be set according to the real adoption situation.
Command format: WD
W
The command key word
D
Input channel alarm mode
0: alarm while one input channel is disconnected
1: alarm while one input channel is disconnected or the time source is
asynchronous (default)
2: alarm while both input channels are disconnected
Command format: W?
To query the current input channel alarm mode.