3 Operation Theory
PCS-9611 Feeder Relay
3-35
Date: 2014-04-08
current (I
2
/I
1
). This will be affected to a lesser extent than the measurement of negative sequence
current alone, since the ratio is approximately constant with variations in load current. Hence, a
more sensitive setting may be achieved.
At the moment when the circuit breaker is closed, because the three poles of the circuit breaker
are discrepant for a very short time, and if the broken conductor protection is enabled, it is easy to
make the broken conductor protection pick up, and it will restore after the load current is stable.
The logic diagram is as shown below. The ratio of I
2
/I
1
is calculated and is compared with the
threshold and if the threshold is exceeded then the delay timer is initiated.
I
2
/I
1
> [50BC.I2/I1_Set]
[50BC.Blk]
[50BC.En]
[50BC.Op]
[50BC.St]
[50BC.En1]
&
t
BCP
0
Figure 3.8-1 Logic diagram of the broken conductor protection
Where:
[50BC.I2/I1_Set] is the ratio setting of the broken conductor protection;
“t
BCP
” is the setting [50BC.t_Op], the time setting of the broken conductor protection;
[50BC.En] is the logic setting of the broken conductor protection;
[50BC.En1] is the binary signal for enabling the broken conductor protection;
[50BC.Blk] is the binary signal for blocking the broken conductor protection.
3.8.2 Broken Conductor Protection Settings
All the settings of the broken conductor protection are listed in the following table. For the
information about the common explanation of the settings, see
Section 7.3
.
No.
Menu text
Explanation
Range
Step
1
50BC.I2/I1_Set
The ratio setting for the broken conductor
protection
0.10~1.00
0.001
2
50BC.t_Op
The time setting for the broken conductor
protection
0~200s
0.001s
3
50BC.En
The logic setting for the broken conductor
protection
0~1
1
4
50BC.OutMap
The output matrix setting of the broken conductor
protection
0x00000 ~
0xFFFFF
1
3.9 Breaker Failure Protection
3.9.1 Breaker Failure Protection Theory
The circuit breaker failure protection is specially applied for re-tripping the circuit breaker, when
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...