13 Maintenance
PCS-9611 Feeder Relay
13-1
Date: 2014-04-08
13.1 Maintenance Schedule
It is recommended that products supplied by NR receive periodic monitoring after installation. In
view of the critical nature of protective relays and their infrequent operation, it is desirable to
confirm that they are operating correctly at regular intervals.
This relay is self-supervised and so requires less maintenance than earlier designs of relay. Most
problems will result in an alarm so that remedial action can be taken. However, some periodic
tests should be done to ensure that the relay is functioning correctly and the extern al wiring is
intact.
13.2 Regular Testing
The relay is almost completely self-supervised. The circuits which can not be supervised are
binary input, output circuits and human machine interfaces. Therefore regular testing can be
minimized to checking the unsupervised circuits.
13.3 Failure Tracing and Repair
Failures will be detected by automatic supervision or regular testing.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the alarm record.
Failures detected by supervision are traced by checking the history alarm reports through the HMI.
See
Section 8.3.2
for the details of the alarm events.
When a failure is detected during regular testing, confirm the following:
Test circuit connections are correct
Modules are securely inserted in position
Correct DC power voltage is applied
Correct AC inputs are applied
Test procedures comply with those stated in the manual
13.4 Replace Failed Modules
If the failure is identified to be in the relay module and the user has spare modules, the user can
recover the protection by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name and hardware type -form as the
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...