![NR Electric PCS-9611 Instruction Manual Download Page 28](http://html1.mh-extra.com/html/nr-electric/pcs-9611/pcs-9611_instruction-manual_1713962028.webp)
2 Technical Data
PCS-9611 Feeder Relay
2-12
Date: 2014-04-08
Apparent Power (VA)
0.05 ~ 1.20×Un, 0.05 ~ 1.40×In
≤ 0.5% of rating
Energy (Wh)
0.05 ~ 1.20×Un, 0.05 ~ 1.40×In
≤ 0.5% of rating at unity power factor
Energy (Varh)
0.05 ~ 1.20×Un, 0.05 ~ 1.40×In
≤ 0.5% of rating at zero power factor
Currents from protection measurement current transformers
Current
0.05 ~ 1.40×In
≤ 2.0% of rating
Voltage
0.05 ~ 1.20×Un
≤ 0.5% of rating
Acti ve power (W)
0.05 ~ 1.20×Un, 0.05 ~ 1.40×In
≤ 3.0% of rating at unity power factor
Reactive Power (Vars)
0.05 ~ 1.20×Un, 0.05 ~ 1.40×In
≤ 3.0% of rating at zero power factor
Apparent Power (VA)
0.05 ~ 1.20×Un, 0.05 ~ 1.40×In
≤ 3.0% of rating
Energy (Wh)
0.05 ~ 1.20×Un, 0.05 ~ 1.40×In
≤ 3.0% of rating at unity power factor
Energy (Varh)
0.05 ~ 1.20×Un, 0.05 ~ 1.40×In
≤ 3.0% of rating at zero power factor
2.3.2 Control Performance
Control mode
Local or remote
Accuracy of local control
≤ 1s
Accuracy of remote control
≤ 3s
2.3.3 Clock Performance
Real time clock accuracy
≤ 3s/day
Accuracy of GPS synchronization
≤ 1ms
External time synchronization
IRIG-B (200-98), PPS or SNTP protocol
2.3.4 Fault and Disturbance Recording
Magnitude and relative phases
≤ 2.5% of applied quantities
Ma ximum duration
10000 sampled points (24 sampled points per cycle)
Recording position
5 cycles before pickup of trigger element
2.3.5 Binary Input Signal
Resolution of binary input signal
≤ 1ms
Binary input mode
Potential-free contact
Resolution of SOE
≤ 2ms
2.3.6 Transient Overreach
Transient overreach (DC offset)
≤ 5% for X/R ≤ 100
2.3.7 Fault Location Function
Tolerance of fault location setting (only OC, ROC and
SOTF elements can trigger the fault location function.)
≤ 5% (metallic short-circuit fault)
2.4 Certification
ISO9001: 2008
Summary of Contents for PCS-9611
Page 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Page 2: ......
Page 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Page 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Page 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Page 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Page 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Page 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Page 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Page 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Page 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Page 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Page 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Page 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Page 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Page 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...