TXMINI-M12-485 / TXMINI-485 TRANSMITTER 

OPERATING MANUAL – V1.0x I 

INTRODUCTION  

TxMini-M12-485

 is a compact temperature transmitter with internal 

connection to temperature sensors Pt100. It consists of an 

electronic circuit encapsulated and a M12 connection for power 

and RS485 communication, which includes the screw thread for 

closing the sensor output. 
You should use an RS485 interface with Modbus RTU commands 

to configure the transmitter. The 

DigiConfig

  software for 

Windows® allows you to configure all features of the transmitter as 

well as its diagnosis, and the possibility of using other Supervisory 

software for configuration and reading of the information provided 

by the device. 

SPECIFICATIONS 

Sensor Input

:

 

Pt100 RTD

:  3-wires connection, current drain of 0.8 mA, 

α

0.00385, according NBR 13773. IEC 60751 (ITS-90). 

Typical accuracy

:

 

0.1 %;

 

Minimum accuracy

: 0.2 %; 

Measuring range

: -200 to 600 ºC; 

Minimum measuring range

: 40 ºC. 

Factory adjusted and calibrated using traceable standards. 
Resistance effect of the sensor wires

: 0.005 °C / 

.

 

Maximum permissible resistance of the sensor wires

: 25 

.

 

Settling time of the measurement

: < 2.5 s.

 

Temperature effect

:

 

<

 

± 

0.2 % / 25 °C. 

Response time

:

 

2 s (typical).

 

Maximum voltage allowed at input terminals no sensor

: 3 V.

 

Power supply

:

 

7 to 40 Vdc, current < 10 mA. 

Operating Temperature

: -40 to 85 °C. 

Ambient humidity

:

 

0 to 90 % UR. 

No electrical isolation between input and output

.

 

Internal protection against polarity inversion of the supply 

voltage

.

 

Connection Wire Cross Section

: 0.14 to 1.5 mm².

 

Screw Tightening

: 0.8 Nm.

 

Housing

: Polyamide. 

Order codes

 

-

 

P/N: 

8806060420

: TxMini-M12-485 Transmitter; 

-

 

P/N: 

8806060430

: TxMini-M12-485-CN

 

Transmitter; 

-

 

P/N: 

8806060520

: TxMini-485 Transmitter (Equipment can only 

be configured during production); 

-

 

P/N: 

8806060530

: TxMini-485-CN Transmitter. 

-

 

P/N: 

8806065000

:  M12 Cable Connector for TxMini-M12 

(accessory). 
 
 
 
 

CONFIGURATION  

Table 1

 shows the default parameters of the transmitter: 

Parameters 

Configuration 

Error Value 

Offset 

0 ºC 

Unit 

ºC 

Digital Filter 

Timer Setting 

60 s 

Baud Rate 

1200  

Data Bits 

8  

Parity 

Par 

Stop Bits 

Address  

247 

Table 1 

- Default parameter values for 

TxMini-M12-485

 

When you use the transmitter with default configuration, none 

intervention is required and its installation can be performed 

immediately. When a change in the configuration parameters is 

necessary, you can do it using 

DigiConfig

  software.  You can 

download the configuration software freely from the manufacturer's 

website. To install it run the "

DigiConfigSetup.exe

" file and follow 

the installer´s instructions. 

Fig. 1

  shows the main screen of 

DigiConfig

 software. 

SOFTWARE CONFIGURATION: 

 

Fig. 1 

TxMini-M12-485 

configuration screen in

 

DigiConfig

 

software 

 

There is no electrical isolation between input and 

output. 

Summary of Contents for TXMINI-M12-485

Page 1: ... to 40 Vdc current 10 mA Operating Temperature 40 to 85 C Ambient humidity 0 to 90 UR No electrical isolation between input and output Internal protection against polarity inversion of the supply voltage Connection Wire Cross Section 0 14 to 1 5 mm Screw Tightening 0 8 Nm Housing Polyamide Order codes P N 8806060420 TxMini M12 485 Transmitter P N 8806060430 TxMini M12 485 CN Transmitter P N 880606...

Page 2: ... Shows the transmitter model Serial Number Shows the transmitter s serial number Firmware Version Displays the firmware version of the device 10 In the Device Configuration field you can check the following items Input Type It indicates the Pt100 sensor used with the TxMini M12 485 transmitter Offset This field allows you to change the value read by the temperature sensor in the range of 10 to 10 ...

Page 3: ...sensor break Overflow If the sensor is reading a temperature value above the allowed measurements for Pt100 sensor the status will indicate overflow Underflow If the sensor is reading a temperature value below the allowed measurements for Pt100 sensor the status will indicate underflow MODBUS COMMANDS Table 4 lists the Modbus RTU commands functions that you can use to supervise or configure the ma...

Page 4: ...us configuration parameters of communication Note TEMPORARY 1200 bps 247 Even For more details please see the previous section Procedure for Temporary Mode REGISTER 22 DIGITAL FILTER Refers to the Digital Filter code set by the user for smooth the variations of the temperature readings The default value for the filter is 0 MECHANICAL INSTALLATION You can install the TxMini M12 485 Transmitter in p...

Page 5: ...del without connector M12 CABLE CONECTION See below guidelines for making or purchasing the M12 cable Fig 7 Connecting pins for M12 cable mounting For appropriate cable resistance compensation the same cable type should be used for all terminals Maximum wire resistance is 25 Ω Usage of a 3 or 4 wire with conductors of equal length and gauge is recommended cable not supplied WARRANTY Warranty condi...