TXMINI-M12-485 / TXMINI-485 TRANSMITTER
OPERATING MANUAL – V1.0x I
INTRODUCTION
TxMini-M12-485
is a compact temperature transmitter with internal
connection to temperature sensors Pt100. It consists of an
electronic circuit encapsulated and a M12 connection for power
and RS485 communication, which includes the screw thread for
closing the sensor output.
You should use an RS485 interface with Modbus RTU commands
to configure the transmitter. The
DigiConfig
software for
Windows® allows you to configure all features of the transmitter as
well as its diagnosis, and the possibility of using other Supervisory
software for configuration and reading of the information provided
by the device.
SPECIFICATIONS
Sensor Input
:
Pt100 RTD
: 3-wires connection, current drain of 0.8 mA,
α
=
0.00385, according NBR 13773. IEC 60751 (ITS-90).
Typical accuracy
:
0.1 %;
Minimum accuracy
: 0.2 %;
Measuring range
: -200 to 600 ºC;
Minimum measuring range
: 40 ºC.
Factory adjusted and calibrated using traceable standards.
Resistance effect of the sensor wires
: 0.005 °C /
Ω
.
Maximum permissible resistance of the sensor wires
: 25
Ω
.
Settling time of the measurement
: < 2.5 s.
Temperature effect
:
<
±
0.2 % / 25 °C.
Response time
:
2 s (typical).
Maximum voltage allowed at input terminals no sensor
: 3 V.
Power supply
:
7 to 40 Vdc, current < 10 mA.
Operating Temperature
: -40 to 85 °C.
Ambient humidity
:
0 to 90 % UR.
No electrical isolation between input and output
.
Internal protection against polarity inversion of the supply
voltage
.
Connection Wire Cross Section
: 0.14 to 1.5 mm².
Screw Tightening
: 0.8 Nm.
Housing
: Polyamide.
Order codes
:
-
P/N:
8806060420
: TxMini-M12-485 Transmitter;
-
P/N:
8806060430
: TxMini-M12-485-CN
Transmitter;
-
P/N:
8806060520
: TxMini-485 Transmitter (Equipment can only
be configured during production);
-
P/N:
8806060530
: TxMini-485-CN Transmitter.
-
P/N:
8806065000
: M12 Cable Connector for TxMini-M12
(accessory).
CONFIGURATION
Table 1
shows the default parameters of the transmitter:
Parameters
Configuration
Error Value
0
Offset
0 ºC
Unit
ºC
Digital Filter
0
Timer Setting
60 s
Baud Rate
1200
Data Bits
8
Parity
Par
Stop Bits
1
Address
247
Table 1
- Default parameter values for
TxMini-M12-485
When you use the transmitter with default configuration, none
intervention is required and its installation can be performed
immediately. When a change in the configuration parameters is
necessary, you can do it using
DigiConfig
software. You can
download the configuration software freely from the manufacturer's
website. To install it run the "
DigiConfigSetup.exe
" file and follow
the installer´s instructions.
Fig. 1
shows the main screen of
DigiConfig
software.
SOFTWARE CONFIGURATION:
Fig. 1
-
TxMini-M12-485
configuration screen in
DigiConfig
software
There is no electrical isolation between input and
output.