Novus TxIsoRail Operation Manual Download Page 1

NOVUS AUTOMATION 

 

1/3 

 

 

 

TxIsoRail 4-20 mA 

MICROPROCESSOR BASED TEMPERATURE TRANSMITTER –  
OPERATION MANUAL V1.0x F 

SPECIFICATIONS 

Sensor input: User defined. The supported sensors are listed in Table 1

along with their maximum ranges. 

Thermocouples:  Types J, K, R, S, T, N, E and B to IEC 60584 (ITS-90). 

 

       Impedance >> 1 M

 

Pt100

Excitation: 180 

µ

A, 2 or 3-wire connection (for 2-wire 

sensors, tie, terminals 2 and 3 together). 

 

    

α

= 0.00385, according to IEC 60751 (ITS-90). 

Voltage

     0 to 50 mVdc, 0 to 10 Vdc. Impedance >> 1 M

Note: 0-10 Vdc input type requires an internal jumper 

switching. 

 

     0 to 20 mA, 4 to 20 mA. Impedance 15.0 

 (+ 1.9 Vdc).

 

Sensor Type 

Range 

Minimum measurement span 

Thermocouple K 

-150 to 1370 °C / -238 to 2498 ºF 

100 °C 

Thermocouple J 

-100 to 760 °C / -148 to 1400 ºF 

100 °C 

Thermocouple R 

-50 to 1760 °C / -58 to 3200 ºF 

400 °C 

Thermocouple S 

-50 to 1760 °C / -58 to 3200 ºF 

400 °C 

Thermocouple T 

-160 to 400 °C / -256 to 752 ºF 

100 °C 

Thermocouple N 

-270 to 1300 °C / -454 to 2372 ºF 

100 °C 

Thermocouple E 

-90 to 720 °C / -130 to 1328 ºF 

100 °C 

Thermocouple B 

500 to 1820 °C / 932 to 3308 °F 

400 °C 

Pt100 

-200 to 600 °C / -328 to 1112 ºF 

40 °C 

Voltage 

0 to 50 mV 

5 mV 

*  

0 to 10 V 

1 V 

Current 

0 to 20 mA 

2 mA 

4 to 20 mA 

2 mA 

Table 1 – Transmitter input sensors 

Output: 2-wire 4-20 mA, linear with respect to the measured signal. 
Resolution: 0.001 mA (14 bits) 
Total Accuracy:  

Better than 0.3 % of the maximum span for 

thermocouples and 0.2 % for Pt100 and voltage; 

Response Time: < 500 ms 
Isolation: Between the sensor and the 4-20 mA loop (1000 V / 1 min). 
Power Supply: 12 to 35 Vdc, across the transmitter; 
Maximum Load (RL):  RL (max.)= (Vdc – 12) / 0.02 [

    Were:  Vdc= Power supply voltage 

Operating Temperature: -40 to 85 °C 
Humidity: 0 to 90 % UR 
Electromagnetic Compatibility: EN 50081-2, EN 50082-2 
Internal protection against polarity inversion. 
Cold junction compensation for thermocouples. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

CONFIGURATION 

If the transmitter is already configured as required by the application (sensor 

type, range, etc), it may be installed and used right away.  However, if a 

distinct configuration is required, this can be done through the TxConfig 

software and the TxConfig Interface
The TxConfig interface and software can be purchased from the manufacturer 

or at its authorized distributors and representatives. Updates for the software 

are available at our website. To install the TxConfig software, run the 

Tx_setup.exe file and follow the instructions. 
Serial port configuration errors may occur when other devices are 

sharing the same port (ex.: Palm Hot Synch). Close all serial port 

applications prior to using the TxConfig software. 
The TxConfig interface connects the transmitter to the PC, as shown in Fig. 

1 and 2. There are two types of interface: TxConfig-RS232 and TxConfig-

USB. 

 

Fig. 1 – TxConfig Interface connections model RS232 

 

Fig. 2 – TxConfig Interface USB connections 

Once the connection is accomplished, the software shows the configuration 

options of the transmitter model attached. Access the Help  for usage 

instructions. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 