NOVUS AUTOMATION 

1/6

 

 

 

 

Transmitters RHT-WM-485-LCD,  

RHT-DM-485-LCD and RHT-P10-485-LCD 

TEMPERATURE AND HUMIDITY TRANSMITTER –  

INSTRUCTIONS MANUAL V1.0x E 

1

 

INTRODUCTION 

The 

RHT-WM-485-LCD

RHT-DM-485-LCD

  and 

RHT-P10-485-LCD

 

transmitters include high precision and stability sensors for measuring 

temperature and relative humidity. They are microprocessed devices and, 

therefore, allow being entirely configured through a RS485 interface, using 

the Modbus RTU commands. The 

DigiConfig

 allows the configuration of all 

transmitter features as well as its diagnostic procedure. 
The transmitter can be configured or displaying the values of measured 

temperature and 

Relative Humidity

 or the values of measured temperature 

and 

Dew Point

1.1

 

IDENTIFICATION 

The identification label is fixed on the transmitter body. Check if the features 

described on this label are in accordance with your order.  
The 

RHT-WM-485-LCD  and RHT-P10-485-LCD

  models  intended for wall 

mounting, while the 

RHT-DM-485-LCD

 model comes with a probe tip rod for 

installation in ducts or through walls. 
The following elements are located at the front side of the transmitter: 

 

Fig. 1

 – Transmitter front 

Communication Indicator  (COM)

:  Indicates when the device is receiving 

data from the Modbus network. 

Button 

 

(Programming)

:  Button used for configuration of the 

communication parameters and for screen changing. 

Temperature

: Value of measured temperature. 

Relative Humidity

: Value of measured relative humidity. 

 

Fig. 2

 – Second transmitter screen 

Communication Address:

 Value programmed for identifying the transmitter 

of the Modbus network. Programmable between 

1

 and 

247

.

 

 
 
 
 
 

2

 

SPECIFICATIONS 

Operating temperature of 

the transmitter 

From -40 °C to 70 °C 
Sensor and Rod (

RHT-DM

): See 

Fig. 3

Electromagnetic 

compatibility 

EM 61326:2000 

Sensor measuring 

range 

Temperature: -40.0 °C to 100.0 °C. 
Relative Humidity (RH): 0.0 to 100.0 % RH. 

(No Condensing) 

Dew Point: -40.0 °C and 100.0 °C 

Measurement accuracy 

See 

Fig. 3

Note

:  a small  measurement error can be 

eliminated adjusting the 

OFFSET

 parameter of 

the software. 

Measuring resolution 

Temperature: 0.1 °C. 

14 bits (16383 levels) 
Relative Humidity (RH): 0.1 %. 

12 bits (4095 levels) 

Response time 

Temperature: up to 30 s in slow air movement. 
Humidity:  up to 8  s in smooth air movement 

(20 to 80 % RH). 

Sampling interval 

3 seconds 

Power supply 

12 Vdc to 30 Vdc, consumption < 16 mA 

Housing 

Polycarbonate 

Protection class 

Product appropriate for applications which 

require protection class up to 

IP65

.  

Electronic module case: IP65; Sensor 

capsule: IP40 

Dimensions 

60 x 70 x 35 mm 

DigiConfig

 software 

operation environment 

Configuration Software for Windows 98, NT, 

2000, XP and Vista. 

Menus in Portuguese, English or Spanish. 

Configures, reads and exhibits data on the 

screen. 

Accessories

 

1.5 m long communication cable is part of the 

product or can be purchased separately (PN: 

8813099999). 

 
 
 
 
 

Summary of Contents for RHT-WM-485-LCD

Page 1: ... communication parameters and for screen changing Temperature Value of measured temperature Relative Humidity Value of measured relative humidity Fig 2 Second transmitter screen Communication Address Value programmed for identifying the transmitter of the Modbus network Programmable between 1 and 247 2 SPECIFICATIONS Operating temperature of the transmitter From 40 C to 70 C Sensor and Rod RHT DM ...

Page 2: ...ble in stainless steel or polyamide 6 6 Fig 4 Flange for fixation of the RHT DM 485 LCD model The probe is made in stainless steel with standard lengths of 150 mm or 250 mm Fig 5 Dimensions of the RHT DM 485 LCD model The RHT WM 485 LCD Wall Mount model is designed for wall mounting Removing the transmitter cover gives the user access to two bores for fixing the base as shown in Fig 6 The transmit...

Page 3: ...tactor and solenoid coils etc 5 CONFIGURATION OPERATION The user will receive the transmitter perfectly calibrated without the need for any adjustments The configuration performed at the factory has the following characteristics Addr Communication Address 247 baVd Communication speed 1200 par Parity Par Stop Bit 1 The DigiConfig for Windows is a software used for configuration of the RHT WM 485 LC...

Page 4: ...ANDS The Modbus RTU commands functions listed in the table below are implemented For further information with respect to each of these commands and the Modbus protocol in general please access the site www modbus org READ HOLDING REGISTERS 0x03 This command can be used for reading the value of one or several holding registers according to the Holding Registers Table WRITE HOLDING REGISTERS 0x06 Th...

Page 5: ...t 3 Indicates temperature only REGISTER 7 TEMPERATURE VALUE ºC or ºF REGISTER 8 RELATIVE HUMIDITY VALUE REGISTER 9 DEW POINT VALUE ºC or ºF Shows the measured value in engineering units The decimal point is fixed at one place the value is exhibited without the decimal point and must be considered by the reading software REGISTER 10 CONFIGURATION OF MEASUREMENT UNIT Defines the measurement unit for...

Page 6: ...sor wash it with water Place the sensor within a 80 C 10 C oven for 24 hours Keep the sensor in a place at a temperature between 20 and 30 C and humidity over 75 RH for 48 hours Place the sensor back in the capsule IMPORTANT The sensor used in this transmitter may be damaged or become out of calibration if it is exposed to chemical agents contaminated atmosphere Hydrochloric Acid Nitric Acid Sulph...